17. Replacing the Non-return Valve

Warning!
All non-return valves must always be replaced as a group.
Failure to observe can result in an increased bacterial load in drinking water and
cause a health risk or even risk of death.
17.1 Close the corner valves (b).
17.2 Trigger the valve.
17.3 Unscrew the connector hoses (a) from the corner valves.
17.4 Take out the grit filters(c).
17.5 Take out the non-return valve (d).
Important!
Be careful to insert the non-return valves and grit filters the right way round.
17.6 Reassemble in the reverse order.

18. Replacing the Solenoid Valve Cartridge

18.1 Close the corner valves.
18.2 Trigger the valve.
18.3 Loosen the screw (a) with an Allan key.
18.4 Pull the housing (b) from the base (d).
18.5 Pull off the hose sleeve (c).
18.6 Remove the screws (f).
18.7 Remove the battery housing (e).
18.8 Take out and replace the solenoid valve cartridge (g).
18.9 Reassemble in the reverse order.

19. Changing the Battery

19.1 Pull off the housing and the hose sleeve (see
19.2 Remove the battery (a) by swivelling it out.
Caution!
Use only 6 V lithium battery type CRP2.
Important!
Ensure correct battery polarity when assembling.
19.3 Reassemble in the reverse order.
Chapter
18.).