ALL THE OPERATIONS DESCRIBED IN THIS SECTION ARE TO BE PERFORMED EXCLUSIVELY BY
QUALIFIED STAFF.
The company declines all liability for damage caused by incorrect connections or operations not
described in this manual.
S
UPS
TORING THE
The storage room must respect the following conditions:
Temperature:
Relative humidity:
P
REPARING FOR INSTALLATION
P
I
RELIMINARY
NFORMATION
UPS models
Rated power
Working temperature
Max. relative humidity during operation
Max. height of installation
W x D x H
Weight (w/ batteries)
Power dissipated at rated resistive load
(pf=0.9) and with battery as buffer *
Power dissipated at rated distortion
load (pf=0.7) and with battery charged *
Flow rate of fans for removing heat from
installation room **
Current leak to earth ***
Isolation protection
Cable input
*
3.97 B.T.U./h = 1 kcal/h
** To calculate the air flow rate, the following formula may be used: Q [m3/h] = 3.1 x P diss [Kcal/h] / (t a - t e ) [°C]
P diss is the power expressed in Kcal/h dissipated by all the devices installed in the installation environment.
ta= ambient temperature, te=outside temperature. To take leaks into account, the value obtained should be increased
by 10%.
The table shows an example of a flow rate with (t a - t e )=5°C and a rated resistive load (pf=0.9).
(Note: This formula is applicable if ta>te, only; if not the UPS installation requires an air-conditioning system).
*** The leakage current of the load is to be added to that of the UPS on the earth wire.
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
INSTALLATION
B
B
AND THE
ATTERY
0°÷40°C (32°÷104°F)
max. 95%
10000 VA
305 Kg
540 kcal/h
2150 B.T.U./h
420 kcal/h
1670 B.T.U./h
340 mc/h
OX
10 kVA
15 kVA
15000 VA
0 ÷ 40 °C
90 % (non-condensing)
1000 m at rated power
(-1% Power for every 100 m above 1000 m)
max 4000 m
440 x 850 x 1320 mm
0.63 kW
0.86 kW
740 kcal/h
2940 B.T.U./h
0.49 kW
0.67 kW
580 kcal/h
2290 B.T.U./h
< 5 mA
IP20
From bottom / on rear
20 kVA
20000 VA
315 Kg
320 Kg
1.15 kW
990 kcal/h
3930 B.T.U./h
0.90 kW
775 kcal/h
3070 B.T.U./h
460 mc/h
615 mc/h
Pag. 62 di 252 + FR