UPS Models
Dimensions and weight
W x D x H
Weight without batteries
Weight with batteries
Modes and efficiency values
Operating modes
AC/AC efficiency in on line mode
AC/AC efficiency in Eco mode
DC/AC efficiency in autonomy mode
Miscellaneous
Noise
Color
(6)
Ambient temperature
(1)
To maintain the output voltage within the range of precision indicated, it may have to be recalibrated after a long period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronized with the mains. If the frequency is outside the
tolerance limits or running on the battery, the frequency is the value selected +0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / mains @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically according to the capacity of the battery installed
(6)
20 – 25 °C for maximum battery life
(7)
@ 100% load & THDv
Battery Box
Battery
Rated voltage per branch
No. batteries / V / Ah
Miscellaneous
(1)
Ambient temperature
Humidity
Protective devices
W x D x H
Weight
(1)
20 – 25 °C for maximum battery life
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
48dB(A)
1%
AB 1320-40B
40/12/9
200 Kg
10 kVA
15 kVA
440 x 850 x 1320 mm
105 Kg
115 Kg
305 Kg
315 Kg
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency)
Frequency Converter
93.5%
92.5%
RAL 7016
0 – 40 °C
AB 1320-80B
240 Vdc
80 / 12 / 9
0 – 40 °C
<95% non-condensing
Overcurrent – Short circuit
400 x 815 x 1320 mm
300 Kg
20 kVA
120 Kg
320 Kg
94%
98%
93.5%
52dB(A)
AB 1320-120B
120 / 12 / 9
400 Kg
Pag. 102 di 252 + FR