I
NSTALLATION SET
ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED PERSONNEL
ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
UPS S
TORAGE
The storage site must meet the following requirements:
Temperature:
Degree of relative humidity:
P
RELIMINARY INFORMATION
UPS Models
Nominal power
Operating temperature
Max relative humidity in
operation
Max installation height
Dimensions L x P x A
Weight
Power loss at nominal
resistive load (pf=0.9) and
with charged batteries
Power loss at nominal
distorting load (pf=0.7) and
with charged batteries
Installation site fan flow
rate for heat removal
Current dispersed to
(3)
ground
Degree of protection
Cable input
(1) 3.97 B.T.U./h = 1 kcal/h
(2) Use the following formula to calculate air flow: Q [mc/h] = 3.1 x P diss [kcal/h] / (t a - t e ) [°C]
P diss is power dissipation expressed in kcal/h in the installation site for all installed equipment.
ta= room temperature, te=external temperature. Increase the value derived by 10% to account for losses.
An example of flow is shown in the table, with (t a - t e )=5°C and with nominal resistive load (pf=0.9).
(Note: This formula is applicable if ta>te; otherwise, installation requires an air conditioner).
(3) The load dispersion current is added to that of the UPS on the ground protection conductor.
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
INSTALLATION
-
UP
-15°-40°C (5°-104°F)
95% max
Safepower Evo-HF 60
60kVA
190kg
2.61 kW
2245 kcal/h
(1)
8910 B.T.U./h
2.41 kW
2070 kcal/h
(1)
8220 B.T.U./h
1400mc/h
(2)
Safepower Evo-HF 80
80kVA
0 - 40 °C
90 % (without condensation)
1000 m at nominal power
(-1% power for every 100 m above 1000 m)
max 4000 m
500 x 850 X 1600 mm
200kg
3.65 kW
3140 kcal/h
12460 B.T.U./h
3.12 kW
2680 kcal/h
10640 B.T.U./h
2000 mc/h
< 300 mA
IP20
at bottom rear
Safepower Evo-HF
100
100kVA
220kg
4.75 kW
4074 kcal/h
16170 B.T.U./h
4.12 kW
3540 kcal/h
14060 B.T.U./h
2600mc/h
Pag. 69 di 272 + FR