ONFIGURING THE
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
Language*
Output voltage
Buzzer
Operating mode**
Battery low **
Date and time**
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
Configurations which can be modified by means of configuration software available at service centres are listed in the
following table.
FUNCTION
Operating mode
Output voltage
Output nominal frequency
Autorestart
Auto power off
Buzzer Reduced
Power share off
Autonomy limitation
Maximum load
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
UPS
DESCRIPTION
Selects mimic panel
language language
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
Selects one of five different
operating modes
Estimated autonomy time
remaining for "battery low"
warning
UPS internal watch setup
Selects one of five different operating modes
Selects the rated output voltage
Selects the rated output frequency
Waiting time for automatic power-on after the return of
Automatic UPS power-off in battery operation mode if the
Selects the audible alarm operating mode
Selects the auxiliary socket operating mode
Maximum battery operation time
Selects the user overload limit
DEFAULT
English
Italian
English
German
French
220V
230V
230V
240V
Normal
Reduced
Reduced: does not sound due to the
momentary intervention of the bypass
ON LINE
ECO
ON LINE
SMART ACTIVE
STAND-BY OFF
3 min.
1 ÷ 7 @1 min step
DESCRIPTION
(Phase - Neutral)
mains voltage
charge is lower than 5%
POSSIBLE CONFIGURATIONS
Spanish
Polish
Russian
Chinese
DEFAULT
ON LINE
230V
50Hz
5 sec.
Disabled
Reduced
Always connected
Disabled
Disabled
Pag. 87 di 252 + FR