Irregular operation of the UPS is very often not an indication of a fault but is simply caused by simple problems or
distractions.
We therefore recommend you consult the table here below, which provides some information that will help you to solve
the most common problems.
WARNING: the table below frequently recommends the use of the maintenance BYPASS. We remind you
that before restoring the UPS to operation, you must make sure that it is on and not in STAND-BY.
If the UPS is in this latter mode, turn on the UPS by accessing the "SYSTEM ON" menu and wait for the
power-on sequence to be completed before removing the maintenance BYPASS.
For further details read the procedures described in the maintenance BYPASS (SWMB) paragraph.
NOTE: For a detailed explanation of the codes listed in the table, see the "STATUS/ALARM CODES" paragraph.
PROBLEM
The UPS WITH THE
MAINS VOLTAGE
PRESENT, DOES NOT
ENTER STAND-BY MODE
(THE RED LOCK/STAND-
BY LED DOES NOT
BLINK, NO BEEP IS
EMITTED AND THE
DISPLAY IS NOT
TURNED ON)
THE LOAD IS NOT
POWERED
THE UPS RUNS ON
BATTERY POWER EVEN
WHEN THE MAINS
VOLTAGE IS PRESENT
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28

TROUBLESHOOTING GUIDE

POSSIBLE CAUSE
NO CONNECTION WITH
INPUT TERMINALS
NO NEUTRAL CONNECTION
1/0 SWITCH BEHIND DOOR IS
SET TO 0
ISOLATOR BEHIND DOOR
(SWIN) IS OPEN
MAINS VOLTAGE NOT
PRESENT (BLACKOUT)
PROTECTIVE DEVICE
UPSTREAM ACTIVATED
NO CONNECTION WITH
OUTPUT TERMINALS
ISOLATOR BEHIND DOOR
(SWOUT) IS OPEN
UPS IS IN STAND-BY
STAND-BY OFF MODE IS
SELECTED
UPS FAILURE AND
AUTOMATIC BYPASS OUT OF
ORDER
PROTECTIVE DEVICE
UPSTREAM ACTIVATED
INPUT VOLTAGE OUTSIDE
TOLERANCE LIMITS FOR
MAINS OPERATION
SOLUTION
Connect the mains to the terminals as indicated in the
installation paragraph
The UPS cannot work without a neutral connection.
WARNING: If this connection is missing, damage could
be caused to the UPS and/or the load.
Connect the mains to the terminals as indicated in the
Installation paragraph.
Set the switch to 1 (if present)
Close the isolator
Check that the mains voltage is present. If necessary,
power on the UPS from the battery to power the load.
Reset the protective device. Warning: check that there
is no overload or short-circuit at the output of the UPS.
Connect the load to the terminals
Close the isolator
Execute the power-on sequence
The mode must be changed. In fact, STAND-BY OFF
(emergency) mode only powers the loads when a black
out occurs.
Insert the maintenance bypass (SWMB) and call your
local service centre
Reset the protective device.
WARNING: Check that there is no overload or short
circuit at the output of the UPS.
Problem caused by the mains. Wait for the input mains
voltage to return within the tolerance limits. The UPS
will return automatically to mains operation.