Installation; Storage Of The Ups; Preparation For Installation; Preliminary Information - Siel SAFEPOWER-EVO-HF 30 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE CARRIED OUT BY QUALIFIED PERSONNEL
ONLY.
The company assumes no responsibility for any damage caused by flawed connections or by operations
that are not described in this manual.
S
TORAGE OF THE
The storage area must respect the following characteristics:
Temperature:
Relative humidity degree:
P
REPARATION FOR INSTALLATION

PRELIMINARY INFORMATION

UPS Models
Nominal power
Operating temperature
Max. relative humidity during operation
Max. installation height
Dimensions W x D x H
Weight with no batteries
Weight with batteries
Dissipated power with nominal resistive load
(pf=0.9) and buffer battery
Dissipated power with nominal distorting load
(pf=0.7) and charged battery
Flow rate of the fans to remove heat from the
(2)
installation area
Current dispersion to earth
Protection level
Cable input
(1) 3,97 B.T.U./h = 1 kcal/h
(2) The following formula can be used to calculate the air flow rate: Q [mc/h] = 3,1 x P diss [kcal/h] / (t a - t e ) [°C]
P diss is the power expressed in kcal/h dissipated by all the devices installed in the installation environment.
ta= ambient temperature, te=external temperature. In order to take leaks into account, it is necessary to increase
the value obtained by 10%.
The table shows an example of a flow rate with (t a - t e ) =5°C and a rated resistive load (pf=0.9).
(Note: This formula is applicable only if ta>te. If not, the UPS installation requires an air-conditioning system).
(3) The dispersion current of the load is added to that of the UPS on earth wire.
IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22

INSTALLATION

UPS
0°÷40°C (32°÷104°F)
95% max
(1)
(1)
(3)
30
Safepower-Evo-HF
30kVA
0 ÷ 40 °C
90 % (no condensation)
1000 m at nominal power rating
(-1% power for every 100 m over 1000 m)
max 4000 m
440 x 850 X 1320 mm
135kg
340kg
1.4 kW
1205 kcal/h
4780 B.T.U./h
1.34 kW
1150 kcal/h
4565 B.T.U./h
750mc/h
< 50 mA
IP20
On the rear from the bottom
40
Safepower-Evo-HF
40kVA
145kg
350kg
1.5 kW
1290 kcal/h
5120 B.T.U./h
1.35 kW
1160 kcal/h
4605 B.T.U./h
800 mc/h
Pag. 64 di 258 + FR