N.B.: The figure shows the contacts present inside the UPS, capable of carrying a max. current of 0.5A to 42Vdc.
The position of the contacts shown in the figure is with no alarm or signal present.
(1)
The output may be programmed using the configuration software.
The function indicated is selected by default (factory setting)
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
NAME
TYPE
15V
POWER
GND
POWER
INPUT #1
INPUT #2
INPUT #3
OUTPUT #1
OUTPUT #2
LOCK
OUTPUT #3
OUTPUT #4

AS400 PORT

Isolated auxiliary power supply, +15V±5% 80mA max
Ground to which the isolated auxiliary power supply (15V)
and the remote commands (Remote ON, Remote BYPASS,
Remote OFF) refer
When pin 2 is connected to pin 15 for at least 3 seconds, the
UPS is turned on
When pin 8 is connected to pin 15, the UPS is powered off
When pin 7 is connected to pin 15, the power supply of the
load switches from inverter to bypass. For as long as the
connection remains, the UPS continues to operate from the
bypass even if the input mains voltage is shut off. If the
jumper is removed when the mains voltage is present, the
UPS resumes operation from the inverter. If the jumper is
removed when there is no mains voltage present, the UPS
resumes operation from the battery
Indicates that the batteries are about to run out when
contact 5/12 is closed
Indicates that the UPS is running on battery power when
contact 6/14 is closed
When the contact is closed, indicates that the UPS is
When the contact is closed, indicates that the load is
powered via the bypass
FUNCTION
instantly
(1)
(1)
(1)
locked
(1)