8 Troubleshooting procedure
If the AESI does not deliver voltage
•
Check mains presence on the mains terminal strip
•
Check the fuses
•
C24: Check the voltage value on terminals USER1 and/or USER2
C38 et C85: Check the voltage value on terminals USER1 and/or USER2 (and/or on each of the 5
outputs on the 5 output card)
•
The voltage on the battery cables must be identical to that of the load
•
Check that each 12 V DC battery has a voltage greater than or equal to 11.5 V DC
•
Repeat the measurement after having disconnected the load and the battery
•
Recheck the signaling of the indicator lights (see chapter 5)
•
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
•
Check the voltage on the battery terminals
•
Check the battery fuse
•
Check the voltage on terminals USER1 and/or USER2 (and/or on each of the 5 outputs on the 5 output
card)
If the indicator lights are not illuminated
•
Check mains presence on the mains terminal strip
•
Check the battery connection (and the battery fuse)
•
Check that the wire ribbon is properly connected
•
Check the voltage on terminals USER1 and/or USER2(and/or on each of the 5 outputs on the 5 output
card)
For additional technical assistance, contact the SLAT hotline
+ 33 (0) 4 78 66 63 70
For return requests, visit our website:
http://en.slat.fr/support-2/rma-customer-service/request-an-rma-number/
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorization) number.
Returns are not accepted without an RMA number.