8 Troubleshooting procedure

If the AESI does not deliver voltage
Check mains presence on the mains terminal strip
Check the fuses
C24: Check the voltage value on terminals USER1 and/or USER2
C38 et C85: Check the voltage value on terminals USER1 and/or USER2 (and/or on each of the 5
outputs on the 5 output card)
The voltage on the battery cables must be identical to that of the load
Check that each 12 V DC battery has a voltage greater than or equal to 11.5 V DC
Repeat the measurement after having disconnected the load and the battery
Recheck the signaling of the indicator lights (see chapter 5)
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
Check the voltage on the battery terminals
Check the battery fuse
Check the voltage on terminals USER1 and/or USER2 (and/or on each of the 5 outputs on the 5 output
card)
If the indicator lights are not illuminated
Check mains presence on the mains terminal strip
Check the battery connection (and the battery fuse)
Check that the wire ribbon is properly connected
Check the voltage on terminals USER1 and/or USER2(and/or on each of the 5 outputs on the 5 output
card)
For additional technical assistance, contact the SLAT hotline
+ 33 (0) 4 78 66 63 70
For return requests, visit our website:
http://en.slat.fr/support-2/rma-customer-service/request-an-rma-number/
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorization) number.