5. UNITS POSITIONING
5.3
Minimum operational
distances of indoor unit
A (mm)
B (mm)
150
150
5.4
Minimum operational
distances of outdoor unit
E
D
A
A
B
C
300
500
300
46
C (mm)
D (mm)
2500
3000
C
B
D
E
2000
500
5.5

Distance between the units

UNIT
Difference
maximum
between
UI e UE
m
XECO-0913
10
XECO-1213
10
XECO-1813
10
XECO-2413
10
XECO-1814D
10
XECO-2414T
10
The two air conditioner units are connected to each other by means
of copper piping. A maximum of 10 curves is allowed and beyond this
number the correct operation and the declared yield of the air conditioner
are not guaranteed.
The two units can be positioned with a maximum gradient of 5 metres.
In cases where the indoor unit is installed higher than the outdoor unit
with: Between 3 and 5 meters must be provided an intermediate siphon
to lock oil.
Warning!
Both pipe-lines must be provided with siphon.
GB
GB
Difference
Charge
minimum
Additional
between
than 5 m
UI e UE
m
g/m
15
20
20
20
25
20
25
20
20
15
20
15
1/2
1/2