Configuration
Data bits to starttec:
In C0410 (selection 6, 7, 8), you can assign the data bits D0, D1 and D2 to internal digital signals.
Data bits from starttec:
In C0415, subcode 5 and 6, you can assign internal digital signals to data bits D0 and D1.
Example:
The starttec will be released via AS−I and a brake motor will then be started. The starttec will report
back the status of the motor and the brake via AS−I.
Data bits to starttec:
AS−I configuration
Bit
Command
D0
Release/inhibit starttec
D1
Start/stop motor
D2
Release/apply brake
Data bits from starttec:
AS−I configuration
Bit
Message
D0
Status of motor
D1
Status of brake
L
Electrical installation
Connection of AS interface
starttec
Comment
parameter setting
D0 = 1:
C0410/10 = 6
D0 = 0:
D1 = 1:
C0410/1 = 7
D1 = 0:
D2 = 1:
C0410/3 = 8
D2 = 0:
starttec
Comment
parameter setting
D0 = 1:
C0415/5 = 3
D0 = 0:
D1 = 1:
C0415/6 = 5
D1 = 0:
EDK71MMXXX−020 DE/EN/FR 5.0
starttec released
(requirement: terminal X3/28 = HIGH)
starttec inhibited
Start motor
Stop motor
Release brake
Apply brake
Motor is running
Motor is stopped
Brake is released
Brake is applied
5