Code
No.
Designation
C0015
Manual setting
s
of operating
mode
C0016
Starting voltage
U
0
1 Motor 1
2 Motor 2
C0040
Inhibit starttec
v
C0043
TRIP reset
v
C0052
Service code
L
Setting options
Lenze
Selection
0
0
Automatic recognition of the
operating mode
1
Ignoring the automatic recognition
Operating mode = operation with
one motor or multi−motor operation
2
Ignoring the automatic recognition
Operating mode = reversal or
operation with pole−changing motor
0.0
à
à
0
starttec inhibited (CINH)
1
starttec released (CINH)
0
Currently no fault
1
Active fault
Potentiometer "T"
EDK71MMXXX−020 DE/EN/FR 5.0
Commissioning
{0.1 %}
100.0
= deactivated
acceleration
time
7
Code table
IMPORTANT
From software version
2.0 onwards
starttec recognises whether
the wiring was performed
for multi−motor operation or
for reversal of the rotation
direction. For operation with
a pole−changing motor or
with motors < 250 W, the
operating mode must be
set manually in C0015.
This setting is essential
when operating with
motors < 250 W in the
operation mode
"reversal"! Otherwise,
the starttec may be
destroyed.
à
Accepts the value from
potentiometer "U
"
0
If C0006 = 0, 1, 4, 5:
l
– Display only
l
If C0006 = 2, 3, 6, 7:
– Starting voltage
adjustable via C0016
à
Accepts the value from
potentiometer "T"
If C0006 = 0, 1, 4, 5:
l
– Display only
l
If C0006 = 2, 3, 6, 7:
– Starting voltage
adjustable via C0016
starttec can only be
released if X3/28 = HIGH
Reset active fault with
C0043 = 0
Changes only through
Lenze Service!
117