Note!
Adhere to the switch−on sequence.
l
In case of faults during commissioning, the chapter on "Troubleshooting"
l
provides support (^ 133).
Switch−on sequence
1.
Ensure that the starttec is inhibited
after mains switch−on
2.
Switch on mains
3.
Switch on 24−VDC supply
4.
Release starttec
5.
Release brake, if necessary
6.
Start the drive
C 2 motors
D Reversal of direction of
rotation
7.
The drive is now running
L
Terminal X3/28 = LOW
Terminal X3/28 = HIGH
Terminal X3/E3 = HIGH
Start motor 1 Terminal X3/E1 = HIGH
Start motor 2 Terminal X3/E2 = HIGH
CINH
E1
M1
E2
M2
E3
t ir
Start motor Terminal X3/E1 = HIGH
CW rotation Terminal X3/E2 = LOW
CCW rotation Terminal X3/E2 = HIGH
CINH
E1
E2
M1
M2
CW
CCW
t ir
EDK71MMXXX−020 DE/EN/FR 5.0
Commissioning
Without hand terminal
Comment
CINH Release starttec via X3/28
E1
M1
E2
M2
E3
t
ir
t
t
t ir
t if
t if
if
start231
CINH Release starttec via X3/28
E1
E2
M1
M2
CW
CCW
t
t ir
t ir
t if
t
ir
start233
t
if
7
Start motor 1
Voltage characteristic at
X1/1U, 1V, 1W (motor 1)
Start motor 2
Voltage characteristic at
X1/2U, 2V, 2W (motor 2)
Brake control at X1/B1, B2
Acceleration time
Deceleration time 0.5 s
(C0013)
Start motor
Reverse direction of
rotation
Voltage characteristic at
X1/1U, 1V, 1W (motor 1)
Voltage characteristic at
X1/2U, 2V, 2W (motor 2)
CW rotation
CCW rotation
Acceleration time
Deceleration time 0.5 s
(C0013)
103