No.
Designation
C0003
Save parameter
v
non−volatile
C0004
Bar graph
display
C0005
Fixed
v
configuration of
input signals
C0006
Transfer
v
HW/*hand
uSEr
terminal
L
Setting options
Lenze
Selection
1
0
Do not save parameter in EEPROM
1
Always save parameter in EEPROM
3
Save separate basic setting in
EEPROM
54
1
54 = apparent current of motor 1 (C0054)
0
0
All digital input signals are supplied
from terminal strip X3
200
All digital input signals are fed from
fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)
255
All digital input signals are fed from
fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)
0
C0012 C0016
0
PT
1
PT
2
PT
3
PT
4
H
5
H
6
H
7
H
EDK71MMXXX−020 DE/EN/FR 5.0
Commissioning
{code no.}
989
C0120
PU
S
PU
H
H
S
H
H
PU
S
PU
H
H
S
H
H
7
Code table
IMPORTANT
Data loss after mains
disconnection
l
Active after every mains
connection
Cyclical changing of
l
parameters via bus
module is not allowed
Subsequently save with
parameter set 1 with
C0002 = 9 as separate
basic setting
Bar graph display shows
l
the selected value in %
after mains connection
Range
l
−180 % ... +180 %
Code is individually
adjustable in four
parameter sets
Sets C0410/x = Lenze
setting
Sets C0410/x = 200
C0410/x was freely
configured
Parameter setting of
l
codes via:
– PU: Potentiometer
"U
" for starting
0
voltage
– PT: Potentiometer "T"
for acceleration time
– S: Stepping switch for
rated motor current
– H: Hand terminal
l
With the parameter
setting via
potentiometer/switch,
you can check the
setting via hand terminal
l
When switching to hand
terminal, the values set
with PU, PT and S are
transferred.
115