7
Commissioning
Code table
Code
No.
Designation
C0135
starttec control
word
(parameter
channel)
120
Setting options
Lenze Selection
Control of starttec via parameter channel.
The most important control commands are
summarised in bit commands
Bit
Assignment
0
Motor 1 start/stop
0 Stop motor 1
1 Start motor 1
1
Select motor 2 start/stop or
direction of rotation
0 Stop motor 2 or CCW rotation
1 Start motor 2 or CW rotation
2
Brake control
0 Release brake
1 Apply brake
3
...
Reserved
8
9
Release/inhibit starttec
0 Release starttec
1 Inhibit starttec
10
Trip set
0 External fault active
1 No fault
11
TRIP reset
1 Þ 0 Edge resets fault
12
...
Reserved
15
EDK71MMXXX−020 DE/EN/FR 5.0
IMPORTANT
C0135 cannot be changed
by using the hand terminal
Sets "External error" fault
EEr
(
, LECOM no. 91)
Cause of malfunction must
be removed