Camille Bauer KINAX HW730 Mode D'emploi page 19

Masquer les pouces Voir aussi pour KINAX HW730:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Pin assignment spring-type terminal block
Pin
1
2
3
1 2 3 4
4
A
A
B
A A B B
B
Assembly instruction cable gland easyCONNECT EMC
Push contact spring with sealing set into the lower part and
tighten nut using a tool. Please make sure that the contact
spring contacts the screen.
Do not electricly modify the device nor
carry out any wiring work when energised.
For work on the electric connection, the
cable has to be separated from the Eth-
ernet switch.
M16x1.5 cable gland is fi xed to the
• The
housing. It may only be used if it is undam-
aged and clean.
The cable gland must not be modifi ed in
any way which is not expressly mentioned
in these operation instructions. In particu-
lar, replacement of the standard sealing
insert by different size is not permissible.
It must be only used with fi xed installed
cables and they must be protected against
shock.
9. Commissioning
Prior to commissioning, check whether the
connection data of the angular position
transmitter agrees with the parameters of
the plant.
The entire plant must be designed EMC-
conform.
9.1 Software installation CB-Manager
A complete parametrization of the device is possible via
confi guration interface only, using the supplied PC software
CB-Manager. The software may also be downloaded free of
charge from our Website www.camillebauer.com.
The fi le "Read-me-fi rst" on the Doku-CD
provides all necessary information for the
installation of the CB-Manager software and
assistance for possible problems.
Camille Bauer Metrawatt
Signal
EIA-568-A
EIA-568-B
Rx-
green/white
orange/white
Rx+
green
orange
Tx-
orange/white
green/white
Tx+
orange
green
blue/white
blue/white
blue
blue
brown/white
brown/white
brown
brown
Operating Instructions HW730 Be
Functionality of the CB-Manager software
The software is primary a tool for the confi guration of diffe-
rent devices (HW730, A
PLUS
and supports the user during commissioning and service. It
allows as well the reading and visualization of measured data.
The CB-Manager software provides a comprehensive help
facility, which describes in detail the operation of the software
as well as all possible parameter settings.
ONLINE- / OFFLINE-parametrization
The parametrization may be performed ONLINE (with existing
connection to the device) or OFFLINE (without connection
to the device). To perform an ONLINE confi guration fi rst the
confi guration of the connected device, and therewith its
hardware version, is read. A modifi ed confi guration can then
be downloaded to the device and stored on the hard disk of
the computer for archiving.
An OFFLINE parametrization can be used to prepare device
confi gurations, to store them on disk and to download it to
the devices, once you are in the fi eld where the devices are
installed. To make this work, the device versions selected
during parametrization must agree with the versions on site.
9.2 Installation of Ethernet devices
Connection
Before devices can be connected to an exi-
sting Ethernet network, you have to ensure
that they will not disturb the normal net-
work service.
None of the devices to connect is allowed
to have the same IP address than another
device already installed
The factory setting of the IP address of the
HW730 is: 192.168.1.101
The network confi guration of the devices is done by means
of the CB-Manager software. As soon as all devices have a
unique network address they may be accessed by means
of a suitable Modbus master client.
Function of the LED's
• ON as soon as a network connection exists
LED 1
• Flashing when data is transmitted via
(green)
Ethernet connection
LED 2
• Flashes when Modbus/TCP packages are
(red)
transferred
Device identifi cation
To have a unique identifi cation of Ethernet devices in a net-
work, to each connection a unique MAC address is assigned.
This address is given on the nameplate, in the example
00 : 12 : 34 : D0 : 00 : 01. Compared to the IP address, which
may be modifi ed by the user any time, the MAC address is
statically.
Network installation using the CB-Manager software
For the subsequent Modbus/TCP communication a unique
network address must be assigned to each of the devices.
This can be done very easily, using the CB-Manager software
to search for devices.
, CAM, VR660, A200R, Vx604s)
19

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Kinax hw730-modbus/tcp

Table des Matières