Earth Resistance Measurement (Two-Wire Method) - Amprobe TELARIS Série Mode D'emploi

Masquer les pouces Voir aussi pour TELARIS Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Earth Resistance Measurement (two-wire method)

The two-wire method consists of measuring the resistance between the earth under test and
a known earth. For this purpose, the PEN conductor of a TN system can be used, for example.
The resistance of the known earth connection has to be subtracted from the measurement
result. This measurement is also feasible in a densely populated or in sealed areas where rods
and auxiliary earth connections may not be installed.
RE
Figure 3: two-wire method
1)
Connect earth to be tested with socket (E) and known earth with socket (H), also refer
to fig. 3
2)
Turn the rotary switch (13) to the "2 pole" position.
3)
Set contact voltage (11) by using key "UL".
4)
If required choose manual frequency selection by using key "auto/man" (16), and
select test frequency with key "f1/f2" (12).
5)
Press key "Start" (14).
6)
Read the measurement result from the display.
• Also refer to display indication
• After the measurement, selection can be made between display of earth resistance or
measurement current (I M ) by using key "Display"(8), depending on the measurement result.
• Possibility to measure conventional resistance by using the grounding resistance
measurement range. For this purpose, connect test leads E and H to the DUT. Test current
is fed via lines E and H, measurement voltage is measured via E and H.
E
R
PEN
PEN
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Telaris earth-test

Table des Matières