AS400 P
ORT
PIN #
1
15
2
8
7
4,5,12
6,13,14
9,10
3,11
N.B.: The figure shows the contacts present inside the UPS, which are capable of carrying a max. current of 0.5A to 42Vdc.
The position of the contact indicated in the figure is with no alarm or signal present.
(1)
The output may be programmed using the configuration software.
The function indicated is selected by default (factory setting)
IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22
NAME
TYPE
15V
POWER
GND
POWER
REMOTE ON
INPUT #1
REMOTE OFF
INPUT #2
REMOTE
INPUT #3
BYPASS
BATTERY LOW
OUTPUT #1
BATTERY
OUTPUT #2
WORKING
LOCK
OUTPUT #3
BYPASS
OUTPUT #4

AS400 PORT

Isolated auxiliary power supply +15V±5% 80mA max
Ground to which the isolated auxiliary power supply (15V)
and the remote commands (Remote ON, Remote BYPASS,
Remote OFF) refer
By connecting pin 2 to pin 15 for at least 3 seconds the UPS
By connecting pin 8 to pin 15 the UPS switches off instantly
By connecting pin 7 to pin 15 the load power supply
switches from inverter to bypass. For as long as the
connection remains, the UPS keeps operating from the
bypass, even if the input mains voltage is absent. If the
jumper is removed in presence of the mains voltage, the
UPS resumes operating from the inverter. If the jumper is
removed in absence of the mains voltage, the UPS resumes
operating from the battery
Indicates that the batteries are about to run out when
contact 5/12 is closed
Indicates that the UPS is running on battery power when
contact 6/14 is closed
When the contact is closed, indicates that the UPS is
When the contact is closed, indicates that the load is
powered via the bypass
FUNCTION
is turned on
(1)
(1)
(1)
locked
(1)
Pag. 92 di 258 + FR