An irregular operation of the UPS is frequently not due to malfunctions, but to simple problems, inconveniences or distractions.
Therefore, the user is advised to consult the table below providing useful information on how to solve the most common
problems.
WARNING: the table below often refers to the use of the maintenance BYPASS. Before restoring the correct
operation of the UPS, make sure that it is switched on and not in STAND-BY.
In case it is in stand-by, turn the UPS on by accessing the "SYSTEM ON" menu, and wait for the start-up sequence
to be completed before removing the maintenance BYPASS.
For further information read carefully the sequence described in the "maintenance BYPASS (SWMB)"
paragraph
NOTE: For the exact meaning of the codes mentioned in the table, please read the "ALARM CODES" section.
PROBLEM
THE UPS CONNECTED
TO THE MAINS, DOES
NOT SWITCH TO STAND
BY MODE
(THE RED
BLOCK/STAND-BY LED
DOES NOT FLASH, NO
BEEP SOUNDS AND THE
DISPLAY DOES NOT
LIGHT UP)
NO POWER REACHES
THE LOAD
THE UPS OPERATES
OFF THE BATTERIES
EVEN THOUGH MAINS
POWER IS PRESENT
IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22

TROUBLESHOOTING

POSSIBLE CAUSE
CONNECTION TO THE INPUT
TERMINAL MISSING
NEUTRAL CONNECTION
MISSING
THE ISOLATOR BEHIND THE
DOOR (SWIN) IS OPEN
MAINS POWER MISSING
(BLACKOUT)
INTERVENTION OF THE
UPSTREAM PROTECTION
DEVICE
CONNECTION TO THE
OUTPUT TERMINAL MISSING
THE ISOLATOR BEHIND THE
DOOR (SWOUT) IS OPEN
THE UPS IS IN STAND-BY
MODE
THE STAND-BY OFF MODE
HAS BEEN SELECTED
MALFUNCTION OF THE UPS
AND AUTOMATIC BYPASS
OUT OF USE
INTERVENTION OF THE
UPSTREAM PROTECTION
DEVICE
THE INPUT VOLTAGE IS
OUT OF THE ALLOWED
OPERATING VALUES FOR
MAINS POWER
SOLUTION
Connect the mains to the terminals following the
indications in the paragraph on Installation
The UPS cannot operate without the neutral
connection. WARNING: The absence of this connection
could damage the UPS and the load.
Connect the mains to the terminals following the
indications in the paragraph on Installation.
Close the isolator
Make sure the mains power is present. If necessary,
perform battery start-up to power the load.
Restore the protection. Warning: make sure there is no
overload or short circuit on the UPS output.
Connect the load to the terminals
Close the isolator
Run the start-up sequence
The operating mode must be changed. In fact the
STAND-BY OFF (emergency) mode only powers the
loads when a black out occurs.
Insert the maintenance bypass (SWMB) and contact
the nearest service centre
Restore the protection.
WARNING: make sure there is no overload or short
circuit on the UPS output.
Problem caused by the mains power. Wait for the input
mains voltage to return within the tolerance limits. The
UPS will return automatically to mains operation.