Faults: These are more critical problems compared to the "Anomalies", as if they persist they may bring the UPS to a
halt even in a very short time.
CODE
F01
F02
F03
F04
F05
F06
F07
F08
F09
F10
F11
F12
F14
F15
F16
F17
F19
F20
F21
F22
F23
F26
F27
F28
F29
F30
F31
F32
F33
F34
F37
F42
F43
F44
IV331 Rev.000 SIEL S.p.A.
Data di emissione: 2011-08-22
DESCRIPTION
Internal communication error
Wrong cyclic sense of the input phases
Phase1 input fuse broken or input relay locked (will not close)
Phase 2 input fuse broken or input relay locked (will not close)
Phase3 input fuse broken or input relay locked (will not close)
Phase 1 input relay locked (will not open)
Phase 2 input relay locked (will not open)
Phase 3 input relay locked (will not open)
Precharge of positive branch condensers failed
Precharge of negative branch condensers failed
BOOST stage anomaly
Wrong cyclic sense of the bypass phases
Inverter phase 1 sine curve distorted
Inverter phase 2 sine curve distorted
Inverter phase 3 sine curve distorted
Inverter stage anomaly
Positive battery overvoltage
Negative battery overvoltage
Positive battery undervoltage
Negative battery undervoltage
Output overload
Phase 1 output relay locked (will not open)
Phase 2 output relay locked (will not open)
Phase 3 output relay locked (will not open)
Phase 1 output fuse broken or output relay locked (will not close)
Phase 2 output fuse broken or output relay locked (will not close)
Phase 3 output fuse broken or output relay locked (will not close)
Battery charger stage anomaly
Battery charger output fuse broken
Heat sink overtemperature
Battery charger overtemperature
BOOST 1 battery fuse broken
BOOST 2 battery fuse broken
BOOST 3 battery fuse broken
Pag. 101 di 258 + FR