Electrical Connections - Camille Bauer SINEAX I552 Mode D'emploi

Masquer les pouces Voir aussi pour SINEAX I552:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Electrical connections

Connect the electrical conductors acc. to the instructions
on type label.
Make sure that all input cables are not live
(potential-free) when making the connec-
tions!
Impending danger by high power supply
voltage!
Take care of current transformers!
Also note that, ...
... the data required to carry out the prescribed
measurement must correspond to those mar-
ked on the nameplate of the SINEAX I552
(
measuring input,
and
power supply, see Fig. 6)!
... the resistance in the output circuit may not over-
range the current output value
R
max. [kΩ] ≤
ext
(I
= current output value)
AN
... and not underrange the voltage output va-
lue
R
min. [kΩ] ≥
ext
... (U
= voltage output value)!
AN
... the measurement output cables should be twisted
pairs and run as far as possible away from heavy
current cables!
In all other respects, observe all local regulations when
selecting the type of electrical cable and installing them!
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 2. For measurement with
1st (lower) measuring range,
power supply connected to
terminals 8 and 9.
10
measuring output
15 V
I
[mA]
AN
U
[V]
AN
2 mA
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 3. For measurement
with 2nd (higher)
measuring range,
power supply connected
to terminals 8 and 9.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 4. For measurement with
1st (lower) measuring range,
power supply connected to the low
tension terminal side
12 and 13.
I
= Measuring input
= Measuring output
= Power supply
Output
Output signal
10
11
12 13
+
4-20 mA
SINEAX I552
0-1/5A / 50/60Hz
0
1A
5A
1
2
3
4 5
Input
Measuring range
Measured quantity
Fig. 6. Declaration to type label.
Symbol
Meaning
Double insulation, device of protection class 2
Test voltage of insulation according to IEC60051:
3,7
AC 3.7 kV
Class icon to the EN60688:
0,5
error limit 0.5% of span
CE conformity mark. The device fulfills the require-
ments of the applicable EC directives.
CSA approved for USA and Canada
file-nr. 204767
Caution!
General hazard point.
Read the operating instructions.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
I
Fig. 5. For measurement
with 2nd (higher)
measuring range, power
supply connected to the
low tension terminal side
12 and 13.
Calibration seal
Camille Bauer AG
0,5
3,7
Switzerland
Mat: 133752 /000000
85-230V AC/DC
50/60Hz 3VA
(+)
+
6
7
8
9
Power
supply

Publicité

Chapitres

Table des Matières
loading

Table des Matières