External enabling contact
Operating mode / Stand-By
In addition to being operated with
the controller, the unit can be
switched on (normal operation)
and switched off (stand-by) via
an external potential-free contact
(normally-closed).
The contact is equipped with a
wire jumper in the factory. The unit
is enabled in this condition.
If the contact is opened, the unit is
disabled and OFF is shown on the
display.
General alarm signal ALARM
230V
The connection of a general alarm
signal, for example, for signalling
or for further processing to a BMS
is possible as standard equipment.
230V is output here.
There is no voltage present at this
contact during normal unit opera-
tion. As soon as a fault is diag-
nosed on the unit, 230V is present
on the respective terminals of the
alarm contact.
Modbus interface RS485
The unit has a Modbus interface
RS485 as standard. This enables
the querying or stipulation of
setpoints, system temperatures,
operating modes etc. A detailed list
of all necessary information can be
obtained on request.
68/44 - K410061801001-00 / 07.2020 -
Terminal blocks
KHS CoolFlow chiller 4.7 (1.6-5.6) kW, Fig. 618 01 001
KHS CoolFlow chiller 7.6 (2.0-10.0) kW, Fig. 618 01 002