B–30
Liste des données ModBus
Code
Nom
Fonc.
A075 PV scale conversion
A076 PV source setting
A077 Reverse PID action
A078 PID output limit
A081 AVR function select
A082 AVR voltage select
A092
Acceleration (2) time
(high)
setting
A092
(low)
A292
Acceleration (2) time
(high)
setting, (2nd motor)
A292
(low)
Registres de maintien pour les fonction du groupe A
R/W
Description
R/W Process Variable (PV) scale
factor (multiplier), range of
0.01 to 99.99
R/W Selects source of Process
Variable (PV), option codes:
00... [OI] terminal (current in)
01... [O] terminal (voltage in)
02... Network
03... Calculate function output
R/W Two option codes:
00... PID input = SP – PV
01... PID input = –(SP – PV)
R/W Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
R/W Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00... AVR enabled
01... AVR disabled
02... AVR enabled except
during deceleration
R/W 200V class inverter settings:
00... 200
01... 215
02... 220
03... 230
04... 240
400V class inverter settings:
00... 380
01... 400
02... 415
03... 440
04... 460
05... 480
R/W Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
R/W
R/W Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3000 sec
R/W
Données du réseau
Registre
Plage
hex
dec.
106Ch 04204
1 to 9999
106Dh 04205
0, 1, 2, 3
106Eh
04206
0, 1
106Fh
04207
0 to 1000
1070h
04208
0, 1, 2
1071h
04209
0 to 5
1074h
04212
1 to
300000
*1
1075h
04213
1518h
05400
1 to
300000
*1
1519h
05401
Res.
0.01
—
—
0.1 %
—
—
0.1 sec