B–32
Liste des données ModBus
Code
Nom
Fonc.
A103 [OI]–[L] input active
range start current
A104 [OI]–[L] input active
range end current
A105 [OI]–[L] input start
frequency enable
A141 A input select for calcu-
late function
A142 B input select for calcu-
late function
A143 Calculation symbol
A145 ADD frequency
A146 ADD direction select
A151 Pot. input active range
start frequency
Registres de maintien pour les fonction du groupe A
R/W
Description
R/W The starting point for the
current input range.
Range is 0. to 100.%
R/W The ending point for the
current input range.
Range is 0. to 100.%
R/W Two options:
00... Use A101 start value
01... Use 0Hz
R/W Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable
R/W Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable
R/W Calculates a value based on
the A input source (A141
selects) and the B input source
(A142 selects). Three options:
00... ADD (A input + B
input)
01... SUB (A input – B input)
02... MUL (A input x B input)
R/W An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
R/W Two options:
00... Plus (adds A145 value to
the output frequency setting)
01... Minus (subtracts A145
value from the output
frequency setting)
R/W The output frequency corre-
sponding to the potentiometer
range starting point,
range is 0.0 to 400.0
Données du réseau
Registre
Plage
hex
dec.
1083h
04227
0 to 100
1084h
04228
0 to 100
1085h
04229
0, 1
108Eh
04238
0 to 4
108Fh
04239
0 to 4
1090h
04240
0 1, 2
1091h
04241
0 to 4000
1093h
04243
0, 1
1095h
4245
0 to 4000
Res.
1 %
1 %
—
—
—
—
0.1 Hz
—
0.1 Hz