System parameters
Parameters Description, values, default value
SOx
Store Output (latching function outputs 1/2)
If the parameter is active, the outputs do not switch back automatically in case of a
change of direction. They must be reset internally or externally.
NOTE: A reset is only possible in the Run mode. A reset deletes the last detected
direction and sets the display to "0DIR".
SO1 applies to output 1, SO2 to output 2.
• Values: 0 = inactive / 1 = front reset ( -button, > 3 s) / 2 = front and external reset
• Default value: 0 (latching function inactive)
ST1
Start-up Delay Time
To suppress fault messages when an installation is started.
Irrespective of the input pulses the respective output is switched during the set time as
defined by the following parameter SC1 when the unit has been switched on or the
24 V signal has been removed from the reset input.
• Values: 0.0...1000.0 s
• Default value: 0.0 (start-up delay inactive)
SC1
Start-up Conditions
In combination with the start-up delay time and the parameter SC1 defined start-up
conditions can be determined:
1
Suppression of the direction signal
During the start-up delay:
After the start-up delay:
2
Set output 1
During the start-up delay:
After the start-up delay:
3
Set output 2
During the start-up delay:
After the start-up delay:
4
Suppression of the signal IN2 before IN1
At the switch-on moment both outputs are OFF.
During the start-up delay:
After the start-up delay:
5
Suppression of the signal IN1 before IN2
At the switch-on moment both outputs are OFF.
During the start-up delay:
After the start-up delay:
6
Set outputs 1 and 2 until the first detection of direction
At the switch-on moment both outputs are ON.
During the start-up delay:
After the start-up delay:
Operating principle without start-up parameters ST1 and SC1:
At the switch-on moment both outputs are OFF.
After power on of the monitor the outputs switch according to the pulse sequence.
IN1 before IN2: Output 1 ON, output 2 OFF (also see example on page 20)
IN1 before IN2: Output 1 ON, output 2 OFF (also see example on page 21)
After an input sequence has been detected the respective output is ON until the
direction changes or a reset time (CT1) has been set.
• Values: 1...6
• Default value: 1 (suppression of the direction signal during the start-up delay)
Output 1 OFF, output 2 OFF
Outputs switch according to the incoming pulse sequence
Output 1 ON, output 2 OFF
Outputs switch according to the incoming pulse sequence
Output 1 OFF, output 2 ON
Outputs switch according to the incoming pulse sequence
Output 1 ON when detecting IN1 before IN2, output 2 OFF
Outputs switch according to the incoming pulse sequence
Output 1 OFF, output 2 ON when detecting IN2 before IN1
Outputs switch according to the incoming pulse sequence
After the first detection of direction the "wrong" relay is
de-energised, e.g. if IN1 before IN2 output 1 remains ON
and output 2 changes to OFF.
Outputs switch according to the incoming pulse sequence
MONITOR
(only in combination with SC1)
(only in combination with ST1)
FD-2