Description
FANS
Ba21
Night minimum ventilation request
Priority between minimum ventilation and night free cooling (FALSE:
minimum ventilation; TRUE: free cooling)
Ba24
Fan K factor for air fl ow calculations
Ba27
Fan fi xed speed request
(0 = SPEED1; 1= SPEED2; 2= SPEED 3) Three speed fan
request in fi xed speed regulation
3 speeds fan type enabled
Three speed fan limit 1
3 speeds fan type enabled
Three speed fan limit 2
3 speeds fan type enabled
Three speed fan limit 3
Ba30
Fan air quality minimum request
Ba33
Fan temperature regulation PID parameters - Proportional gain
Fan temperature regulation PID parameters - Integral time
Ba36
Proportional gain
Integral time
Dead band
Supply air fl ow deadband
Dead band
Bb01
Supply fan request in case of air pressure probe error
Bb03
Minimum fan speed during antifreeze
Bb06
Supply fan: Minimum regulation value
Supply fan: Maximum regulation value
Bb09
Automatically generated - Time in [s]for a positive change for Ebm-
papst fan
Automatically generated - Time in [s] for a negative change of set
value for Ebmpapst fan
Automatically generated - Preferred running direction (FALSE: left;
TRUE: right) for Ebmpapst fan
Bb12
Settings of the emergency function - Enable emergency function
(FALSE: Inactive; TRUE: Active; ) for Ebmpapst fan
Fan speed in emergency in rpm
Settings of the emergency function - Time in ms before entering in
emergency mode for Ebmpapst fan
Bb15
Serial interface settings (Address, baudrate, parity confi guration) -
Network address for Ebmpapst fan
Serial interface settings (Address, baudrate, parity confi guration) -
Enable change address procedure
Automatically generated - 0:Check condition;1: Write new addr.;
2: Reboot fan fi rmware; 3: Wait offl ine; 4: Reset communication and
wait online status;5:Reset procedure;
Bb18
Serial interface settings (Address, baudrate, parity confi guration) -
Baudrate [bps] for the communication with the fan. (0=1200, 1=2400,
2=4800, 3=9600, 4=19200, 5=38400, 6=57600, 7=115200)
Serial interface settings (Address, baudrate, parity confi guration) -
Parity confi guration ready to be sent via modbus (0 = 8E1; 1 = 8O1;
2= 8N2; 3 = 8N1)
Serial interface settings (Address, baudrate, parity confi guration)
- Enable change communication interface fan settings (baudrate,
parity, stop bit)
Automatically generated - 0:Idle; 1: Write password; 2:Write parame-
ters; 3:Send adopt parameters; 4:Wait offl ine; 5:Reset procedure;
Bb21
Serial interface settings (Address, baudrate, parity confi guration) -
Frame timeout (ms)
Serial interface settings (Address, baudrate, parity confi guration) -
Command delay time (ms)
Bb24
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Ramp up timing for ZiehlAbegg fan [s]
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Ramp down timing for ZiehlAbegg fan [s]
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Running direction (FALSE=clockwise, TRUE=counter-clockwise)
Bb27
Serial interface parameters (timeout, command delay, etc.)
- Fan Network address
Serial interface parameters (timeout, command delay, etc.)
- Start changing procedure of fan address
Fan status (working mode, errors) - Status of the COM parameter
changing procedure
116
Tableau des paramètres
Dev
Min
Max
UoM
50.0
0.0
100.0
-
FALSE
0
1
-
100.0
0.0
99999.0
-
30.0
0.0
100.0
%
2
0
2
-
-
0
1
-
33.0
0.0
FansThree-
%
Speed2
-
0
1
-
66.0
FansThree-
FansThree-
%
Speed1
Speed3
-
0
1
-
100.0
FansThree-
100.0
%
Speed2
10.0
0.0
100.0
%
8.0
-999.9
999.9
-
120
0
65535
-
8.0
0.0
999.9
-
120
0
999
-
0.0
-999.9
999.9
-
0.0
0.0
3000.0
m^3/h R/W HR1518
0.0
-999.9
999.9
-
25.0
0.0
100.0
-
10.0
0.0
100.0
%
0.0
0.0
100.0
%
100.0
0.0
100.0
%
10
0
625
s
10
0
625
s
FALSE
0
1
-
FALSE
0
1
-
0
0
MaxSpeed
-
5000
0
65535
ms
30
0
999999
-
-
0
1
-
-
0
9
-
4
0
9
-
2
0
3
-
-
0
1
-
-
0
9
-
500
0
9999
ms
4
0
9999
ms
0
0
625
-
0
0
625
-
FALSE
0
1
-
30
1
247
-
-
0
1
-
-
0
9
-
Dir Modbus BACnet
R/W HR1505
AV3006
R/W CS249
BV249
R/W HR1506
AV3007
R/W HR1507
AV3008
R/W HR1508
PIV3009
R
DI704
BV1162
R/W HR1509
AV3010
R
DI704
BV1162
R/W HR1510
AV3011
R
DI704
BV1162
R/W HR1511
AV3012
R/W HR1512
AV3013
R/W HR1513
AV3014
R/W HR1514
PIV3015
R/W HR1515
AV3016
R/W HR1516
PIV3017
R/W HR1517
AV3018
AV3019
R/W HR1517
AV3018
R/W HR1563
AV3063
R/W HR1564
AV3064
R/W HR1896
AV3376
R/W HR1897
AV3377
R/W HR1565
PIV3065
R/W HR1566
PIV3066
R/W CS254
BV254
R/W CS255
BV255
R/W HR1567
IV3067
R/W HR1569
PIV3068
R/W HR1570
PIV3069
R/W CS256
BV256
R
IR515
PIV3829
R/W HR1572
PIV3070
R/W HR1573
PIV3071
R/W CS257
BV257
R
IR516
PIV3830
R/W HR1574
PIV3072
R/W HR1576
PIV3073
R/W HR1578
PIV3074
R/W HR1579
PIV3075
R/W CS258
BV258
R/W HR1580
PIV3076
R/W CS259
BV259
R
IR517
PIV3831