Carel k.Air large Manuel D'utilisation page 120

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FRE
Rif
Description
AUXILIARY REGULATION
H005
Auxiliary Regulation 1 - Setpoint selection
Auxiliary Regulation 1 - Regulation setpoint
Auxiliary Regulation 1 - Modulating: Low limit
Auxiliary Regulation 1 - Dout: Diff erential
Auxiliary Regulation 1 - Modulating: High limit
Auxiliary Regulation 1 - Enable comfort auxiliary regulation
H007
Auxiliary Regulation 1 - Modulating: Kp
Auxiliary Regulation 1 - Modulating: Integral time
Auxiliary Regulation 1 - Modulating: Derivative time
Auxiliary Regulation 1 - Modulating: Dead Band
H009
Auxiliary Regulation 1 - Reverse mode
Auxiliary Regulation 1 - Cooling/Heating mode
H011
Auxiliary Regulation 2 - Input selection
Auxiliary Regulation 2 - Output selection
H013
Auxiliary Regulation 2 - Dout: Error value
Auxiliary Regulation 2 - Modulating: Error value
Auxiliary Regulation 2 - Enable selection
Auxiliary Regulation 2 - Enable selection: Manual enabling
H015
Auxiliary Regulation 2 - Setpoint selection
Auxiliary Regulation 2 - Regulation setpoint
Auxiliary Regulation 2 - Modulating: Low limit
Auxiliary Regulation 2 - Dout: Diff erential
Auxiliary Regulation 2 - Modulating: High limit
Auxiliary Regulation 2 - Enable comfort auxiliary regulation
H017
Auxiliary Regulation 2 - Modulating: Kp
Auxiliary Regulation 2 - Modulating: Integral time
Auxiliary Regulation 2 - Modulating: Derivative time
Auxiliary Regulation 2 - Modulating: Dead Band
H019
Auxiliary Regulation 2 - Reverse mode
Auxiliary Regulation 2 - Cooling/Heating mode
H021
Auxiliary Regulation 3 - Input selection
Auxiliary Regulation 3 - Output selection
H023
Auxiliary Regulation 3 - Dout: Error value
Auxiliary Regulation 3 - Modulating: Error value
Auxiliary Regulation 3 - Enable selection
Auxiliary Regulation 3 - Enable selection: Manual enabling
H025
Auxiliary Regulation 3 - Setpoint selection
Auxiliary Regulation 3 - Regulation setpoint
Auxiliary Regulation 3 - Modulating: Low limit
Auxiliary Regulation 3 - Dout: Diff erential
Auxiliary Regulation 3 - Modulating: High limit
Auxiliary Regulation 3 - Enable comfort auxiliary regulation
H027
Auxiliary Regulation 3 - Modulating: Kp
Auxiliary Regulation 3 - Modulating: Integral time
Auxiliary Regulation 3 - Modulating: Derivative time
Auxiliary Regulation 3 - Modulating: Dead Band
H029
Auxiliary Regulation 3 - Reverse mode
Auxiliary Regulation 3 - Cooling/Heating mode
H031
Auxiliary Regulation 4 - Input selection
Auxiliary Regulation 4 - Output selection
H033
Auxiliary Regulation 4 - Dout: Error value
Auxiliary Regulation 4 - Modulating: Error value
Auxiliary Regulation 4 - Enable selection
Auxiliary Regulation 4 - Enable selection: Manual enabling
H035
Auxiliary Regulation 4 - Setpoint selection
Auxiliary Regulation 4 - Regulation setpoint
Auxiliary Regulation 4 - Modulating: Low limit
Auxiliary Regulation 4 - Dout: Diff erential
Auxiliary Regulation 4 - Modulating: High limit
Auxiliary Regulation 4 - Enable comfort auxiliary regulation
H037
Auxiliary Regulation 4 - Modulating: Kp
Auxiliary Regulation 4 - Modulating: Integral time
Auxiliary Regulation 4 - Modulating: Derivative time
Auxiliary Regulation 4 - Modulating: Dead Band
H039
Auxiliary Regulation 4 - Reverse mode
Auxiliary Regulation 4 - Cooling/Heating mode
120
Tableau des paramètres
Dev
Min
Max
UoM
0
0
4
-
20.0
-9999.9
9999.9
-
0.0
0.0
100.0
-
20.0
0.0
999.9
-
100.0
0.0
100.0
-
FALSE 0
1
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
0.0
0.0
999.9
-
FALSE 0
1
-
FALSE 0
1
-
0
0
13
-
0
0
1
-
FALSE 0
1
-
0.0
0.0
100.0
-
0
0
5
-
FALSE 0
1
-
0
0
4
-
20.0
-9999.9
9999.9
-
0.0
0.0
100.0
-
20.0
0.0
999.9
-
100.0
0.0
100.0
-
FALSE 0
1
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
0.0
0.0
999.9
-
FALSE 0
1
-
FALSE 0
1
-
0
0
13
-
0
0
1
-
FALSE 0
1
-
0.0
0.0
100.0
-
0
0
5
-
FALSE 0
1
-
0
0
4
-
20.0
-9999.9
9999.9
-
0.0
0.0
100.0
-
20.0
0.0
999.9
-
100.0
0.0
100.0
-
FALSE 0
1
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
0.0
0.0
999.9
-
FALSE 0
1
-
FALSE 0
1
-
0
0
13
-
0
0
1
-
FALSE 0
1
-
0.0
0.0
100.0
-
0
0
5
-
FALSE 0
1
-
0
0
4
-
20.0
-9999.9
9999.9
-
0.0
0.0
100.0
-
20.0
0.0
999.9
-
100.0
0.0
100.0
-
FALSE 0
1
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
0.0
0.0
999.9
-
FALSE 0
1
-
FALSE 0
1
-
Dir Modbus BACnet
R/W HR1588
PIV3083
R/W HR980
AV2502
R/W HR1589
AV3084
R/W HR1590
AV3085
R/W HR1591
AV3086
R/W CS263
BV263
R/W HR1592
AV3087
R/W HR1593
PIV3088
R/W HR1594
PIV3089
R/W HR1595
AV3090
R/W CS264
BV264
R/W CS265
BV265
R/W HR1597
PIV3092
R/W HR1598
PIV3093
R/W CS268
BV268
R/W HR1599
AV3094
R/W HR1600
PIV3095
R/W CS269
BV269
R/W HR1601
PIV3096
R/W HR1602
AV3097
R/W HR1603
AV3098
R/W HR1604
AV3099
R/W HR1605
AV3100
R/W CS270
BV270
R/W HR1606
AV3101
R/W HR1607
PIV3102
R/W HR1608
PIV3103
R/W HR1609
AV3104
R/W CS271
BV271
R/W CS272
BV272
R/W HR1611
PIV3106
R/W HR1612
PIV3107
R/W CS275
BV275
R/W HR1613
AV3108
R/W HR1614
PIV3109
R/W CS276
BV276
R/W HR1615
PIV3110
R/W HR1616
AV3111
R/W HR1617
AV3112
R/W HR1618
AV3113
R/W HR1619
AV3114
R/W CS277
BV277
R/W HR1620
AV3115
R/W HR1621
PIV3116
R/W HR1622
PIV3117
R/W HR1623
AV3118
R/W CS278
BV278
R/W CS279
BV279
R/W HR1625
PIV3120
R/W HR1626
PIV3121
R/W CS282
BV282
R/W HR1627
AV3122
R/W HR1628
PIV3123
R/W CS283
BV283
R/W HR1629
PIV3124
R/W HR1630
AV3125
R/W HR1631
AV3126
R/W HR1632
AV3127
R/W HR1633
AV3128
R/W CS284
BV284
R/W HR1634
AV3129
R/W HR1635
PIV3130
R/W HR1636
PIV3131
R/W HR1637
AV3132
R/W CS285
BV285
R/W CS286
BV286
Tab. 10.h