Device Versions; Structure And Function - Burkert 2730 Manuel D'utilisation

Masquer les pouces Voir aussi pour 2730:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.2.1. Device versions
actuator sizes
The piston-controlled diaphragm control valve is available for the
following actuator sizes:
ø 80 mm, ø 100 mm, ø 125 mm.
pilot pressure
Designs with lower pilot pressure (reduced spring force) are
available on request.
Contact your Bürkert sales office or our Sales Center, e-mail:
info@de.buerkert.com
5.3.
structure and function
The operation of the diaphragm control valve Type 2730 / 2731
/ 2731K is possible only in combination with an control unit.
Possible control units are:
Positioner Type 8630, 8635, 8692, 8694, 8792
Process controller Type 8693, 8793
5.3.1. structure
The piston-controlled diaphragm control valve consists of a pneu-
matically operated piston actuator and a 2/2-way valve body.
10
english
Type 2730 / 2731 / 2731K
Product description
Fig. 3:
Structure and description
5.3.2. function / control functions (cf)
Spring force (CFA) or pneumatic pilot pressure (CFB) generates the
closing force on the diaphragm pressure piece. The force is transferred
via a spindle which is connected to the actuator piston.
control function a (cfa)
Normally closed by spring action
control function B (cfB)
Normally open by spring action
Actuator cover
Actuator body
Upper pilot air port
Lower pilot air port
Diaphragm socket
Diaphragm
Line connection
Diaphragm body

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

27312731kDn 15Dn 50

Table des Matières