Input Data
MPP voltage range
Input voltage range (at 1,000 W/m²/14 °F in an open circuit)
Max. input current (MPP1/MPP2)
(MPP1 + MPP2)
Max. short circuit current of solar modules (I
Max. backfeed current from AC grid
Output Data
Nominal output power (P
Max. output power (+104°F)
Max. output power (+140°F)
Phases
Nominal grid voltage
Operating range AC voltage
Adjustment range for grid voltage
Max. continuous output current at V
AC recommended min. overcurrent protection
Max. output residual current per duration
Nominal frequency
Total harmonic distortion
Power factor (cos phi)
General Data
Maximum efficiency
CEC efficiency
Cooling
Protection class
Dimensions h x w x d
Weight (full/lite version)
Permissible ambient temperature
Permissible storage temperature
Permissible humidity
Noise emission
Protection Devices
Reverse polarity protection
Stand-alone operation protection
Arc detection/interruption
64
SC PV
1)
)
nom
nom
450 - 800 V DC
) (MPP1/MPP2)
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
20.0-3 480
500 - 800 V DC
200 - 1,000 V DC
33.0/25.0 A
51 A
49.5/37.5 A
2)
0.0 A
19,995 W
19,995 W
12,200 W
14,400 W
3 ~ NPE
254 V/440 V
277 V/480 V
-12 ... +10%
127 - 322 V/220 - 558 V
26.2 A
24.0 A
35.0 A
30.0 A
30.9 A/150.4 ms
50/60 Hz
< 1%
3)
0 - 1 ind./cap.
98.00%
97.50%
Controlled forced-air ventilation
NEMA 4X
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
95.7/95.0 lbs. (43.4/43.1 kg)
-40°F to +140°F (-40°C to +60°C)
-40°F to +158 °F (-40°C to +70 °C)
0 - 100%
65 dB(A) (ref. 1pW)
Integrated
Integrated
Integrated
22.7-3 480
22,727 W
22,727 W
12,200 W
14,400 W
29.8 A
27.3 A
40.0 A
35.0 A
< 1.25%
97.50%