RELAY CONFIGURATION

The Battery Monitor integrates a configurable electrical contact on the channel 1 alarms. It
can perform the control of a generator set. (see Characteristics of the contact)
To access to the relay configuration menu, when
1
you are viewing the status of yours power sources
and batteries, press the button
setup menu appears on the screen.
Select the menu « Relay Configuration », and
2
press _
OK
_.
Information on the relay configuration settings:
Parameters
Relay Type
Relay Activation Type
Relay Deactivation
_MENU_. The
Choice of settings
• Pulse (10 sec)
• Active
• Passive
• OFF
• Low Capacity
• Low Capacity or Low
Voltage
• Low Voltage
• Manual
• 1 to 100%
Battery Monitor JBNUM II - CPS3
Principle
Pulse : the relay coil is supplied for 10 seconds at the
detection of the alarm.
Passive : the relay coil is supplied at the detection of the
alarm. The relay coil is de-supplied depending on the
configuration parameter « Relay Deactivation ».
Active : the relay coil is de-supplied at the detection of
the alarm. The relay coil is supplied depending on the
configuration parameter « Relay Deactivation ».
The user can choose between 3 types of alarms to
activate the relay.
The deactivation of the relay can be done in 2 ways :
- Manual shutdown > Hold the button
seconds.
- Shutdown on capacity : the relay is deactivated when
the battery 1 capacity achieved to a threshold defined
by « Relay Deactivation ».
52
for 3