Installation Conditions And Preparations; Appliance Installation - Stiebel Eltron WTS 30 E Utilisation Et Installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Installation
Installation
7.3.2 dHw cylinder circuit
5
4
3
2
1
1 Ball valve
2 Circulation pump
3 Flushing, drain and fill connection
4 Plate heat exchanger
5 Safety valve
6 Non-return valve
7.4
standard delivery wts 40
Delivered with the appliance are:
- Wall mounting bracket
- Screws 8x70
- Screws 8x100
- Washers
- Rawl plugs
- Upper shell, thermal insulation
- Lower shell, thermal insulation
- 2 ball valves
wWW.STIeBel-elTROn.cOM
8.
installation
8.1

installation conditions and preparations

Ensure that:
- The pipe runs are kept as short as possible.
- The selected pipe cross-sections are not smaller than the
connections at the appliance.
CAUTION Risk of damage through foreign bodies
!
Ensure that the system is flushed.
CAUTION Risk of damage through corrosion
!
Copper solder is used inside the heat exchanger.
6
Therefore ensure that no steel pipes are used in the flow
direction downstream of the heat exchanger. Dissolved
1
copper ions could result in pitting corrosion in steel.
9.
installation
9.1

appliance installation

f Remove the packing material and lift the upper shell of the
f
thermal insulation from the appliance.
f Lift the appliance out of the lower shell of the thermal
f
insulation.
f Insert both wall mounting brackets from the back into the
f
lower shell of the thermal insulation and click into place.
f Position the lower shell at the required installation location.
f
f Right the lower shell plumb using a spirit level.
f
f Mark out the holes to be drilled for the wall mounting
f
bracket and for the lower shell on the wall, then remove the
lower shell again with its mounting brackets from the wall.
f
f
Drill the holes and insert rawl plugs.
WTS | 17

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wts 40 e

Table des Matières