Installation
Exhaust
System Maintenance
The dryer interior and the complete
exhaust system
should be inspected
after one year of use and cleaned
if necessary.
Inspect and clean exhaust duct every one
to two years as required
thereafter.
The weather
hood
should be checked
frequently
to make sure the
dampers
move freely, dampers
are not pushed in and
that nothing has been set against them. This
maintenance
work should be done by a qualified
service person.
WARNING
To reduce the risk of electric
shock,
disconnect
the electrical
service
to the
dryer before cleaning.
W043
Exhausting
the dryer in hard-to-reach
locations
can be
accomplished
by installing
the 521 P3 Flexible
Metal
Vent Kit, available
as optional equipment
at extra cost.
The kit comes in two halves that can be separately
attached to the dryer and wall outlet. Once attached,
the dryer can be slid back into position
and the two
halves connected
from the front.
521P3 FLEXIBLE METAL VENT KIT
Figure 22
D6241
Dryer Airflow
Efficient
dryer operation requires proper dryer airflow.
Proper dryer airflow can be evaluated
by measuring
the static pressure.
Static pressure
in the dryer's
exhaust duct should be no
greater than that shown in Figure 23. (Check with
dryer running
and no load.)
NOTE:
This can be measured
with a manometer
placed
on the exhaust
duct approximately
two feet
(61 cm) from the dryel. Refer to Figure 23.
MAXIMUM STATIC
PRESSURE IN
WATER COLUMN
0.6 in. (1.5 cm)
1
2
MEASURING STATIC PRESSURE
Manometer
Exhaust Duct
D0121
Figure 23
512023
© Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT
27