4.6
Setup mode
It is possible to change some parameters of the UPS while the UPS is in standby or in normal mode.
Press and hold the
Use the
button to enter the parameter to be changed. As confirmation, the value on the digits will
start to flash. Press the
and
buttons to change the values of the parameter and confirm the value with the
As confirmation, there is one beep and the value on the digits stop to flash.
To exit the setup mode, press and hold the
minute the UPS exits from the setup mode.
The following tables indicate the parameters that can be set in standby mode and in normal mode.
FUNCTION
SET +
EPO
SET + BATT + NUM
SET + OUT + V
SET + IN + OUT
INDICATION
If there are external battery cabinets installed, it is important to set up the total number of strings installed
to have a correct calculation of the backup time in stored energy mode.
The UPS has always 1 string installed. The external battery cabinets have the following number of
strings: 3 110 74 and 3 110 75 - 2 strings ; 3 110 76 and 3 100 77 - 1 string.
button for 3 seconds until there is one beep is heard and the SET icon is shown.
button to exit from the parameter. While the selected value flashes, use
STANDBY MODE
EPO: Emergency auxiliary contact to turn off the UPS in case of
Total number of battery strings installed (internal + external)
Installation and User Manual
button for 3 seconds. If no button is pressed, after 1
DESCRIPTION
Buzzer
Possible values: on / oFF
Default: on
Setting for the EPO auxiliary contact.
Main page
emergency
Subpage
nC: contact normally closed
nO: contact normally opened
Default: EPO nC
Possible values:
• 1 to 9 (1000VA and 1500VA)
• 1 to 5 (2200VA and 3000VA)
Default: 1
(only for 2U/3U)
Output voltage
Possible values: 200/208/220/230/240 V
Default: 230V
Auto Restart function
Possible values: on / oFF
Default: on
KEOR SPE R/T
button.
54