HSI 90/HSI 150. How to set in concrete correctly.
6
Installation: For duct/conduit connection with spacer HSI-AH 40
For duct/conduit connection (Da ≥ 160 mm), we recom-
1
mend to use the spacer HSI-AH 40 (accessory) when in-
stalling HSI 150 wall insert packages.
For planned cable conduit sections and pipes with an
outer diameter of ≥ 160 mm (connection via HSI 150-M168
(WR), HSI 150-D 160 GSM, KES-M 150-D or HSI 150-GSM
160/X), this ensures a greater level of compaction in the
protective pipe trench and ensures that the minimum
protective pipe distance of ≥ 50 mm is clearly maintained.
Plug together the HSI 150 wall inserts by means of the HSI-
2
AH spacer to achieve the requested packaging. In each
contact surface of the assembly frame one spacer has to be
installed.
HSI 150 and HSI 90 wall inserts can be plugged
together using the spacers HSI-AH 40.
Provided that no HSI-AH 40 spacers are used – due
to lack of space, for example – it is essential to
take greater care when setting in concrete and
when compacting the duct/conduit trenches in
order to avoid damage to cable conduit sections
caused by settlements concrete compaction!
Packaging e.g. HSI 150 - 2 x 3 - K2/X
with spacer
Packaging e.g. HSI 150 - 2 x 3 - K2/X with
spacer and pipe connection �
mm, e.g. via HSI 150-D160 GSM.