HSI 90/HSI 150. How to set in concrete correctly.
6
Installation: For duct/conduit connection with spacer HSI-AH 40
For duct/conduit connection (Da ≥ 160 mm), we recom-
1
mend to use the spacer HSI-AH 40 (accessory) when in-
stalling HSI 150 wall insert packages.
For planned cable conduit sections and pipes with an
outer diameter of ≥ 160 mm (connection via HSI 150-M168
(WR), HSI 150-D 160 GSM, KES-M 150-D or HSI 150-GSM
160/X), this ensures a greater level of compaction in the
protective pipe trench and ensures that the minimum
protective pipe distance of ≥ 50 mm is clearly maintained.
Plug together the HSI 150 wall inserts by means of the HSI-
2
AH spacer to achieve the requested packaging. In each
contact surface of the assembly frame one spacer has to be
installed.
•
HSI 150 and HSI 90 wall inserts can be plugged
together using the spacers HSI-AH 40.
•
Provided that no HSI-AH 40 spacers are used – due
to lack of space, for example – it is essential to
take greater care when setting in concrete and
when compacting the duct/conduit trenches in
order to avoid damage to cable conduit sections
caused by settlements concrete compaction!
Packaging e.g. HSI 150 - 2 x 3 - K2/X
with spacer
Packaging e.g. HSI 150 - 2 x 3 - K2/X with
spacer and pipe connection �
mm, e.g. via HSI 150-D160 GSM.