OCD5/MCD5-1999 / OWD5/MWD5-1999
The sensor cable may be extended up to 100 m by means of a
separate two-core cable. Two vacant wires in a multi-core cable
used, for example, to supply current to the floor heating cable must
not be used. The switching peaks of such current supply lines
may create interference signals that prevent optimum thermostat
function. If a shielded cable is used, the shield must not be
connected to earth (PE). The two-core cable must be placed in a
separate pipe or segregated from power cables in some other way.
Mounting of thermostat with built-in sensor
The room sensor is used for comfort temperature regulation in
rooms. The thermostat should be mounted on the wall approx.
1.5 m above the floor in such a way as to allow free air circulation
around it. Draughts and direct sunlight or other heat sources must
be avoided.
Fig. 4 - Opening the thermostat
1. Slide the power button down to Off "0".
2. Release the front cover ONLY by inserting a small screwdriver
into the slot at the centre of the bottom side of the front cover to
press and hold the catch securing the front cover.
3. Then carefully pull the front cover away, initially from the
lower part of the thermostat, then from the upper part of the
thermostat.
Fig. 5 - Connections
Connect the wires in accordance with the diagram. The wires must
be connected as follows:
Term. 1:
Term. 2:
Term. 3-4:
Term. X:
Term. 5-6:
Fig. 6 + 7 - Mounting the thermostat
1. Mount the thermostat in the wall socket.
2. Fit the frame and carefully press the cover onto the thermostat
- starting with the upper part of the cover, then the lower part of
the cover. Ensure that both the power slide button on the cover
and the power switch pin in the thermostat are down.
Neutral (N)
Live (L)
Output, max. 16 A
Do not connect
External floor sensor
© 2021 OJ Electronics A/S
English
9