1. DEVICE PRESENTATION

Controller type

TControl POD glass EC

2. TECHNICAL DATA

Measured value
Temperature
Modbus RS485; Transmission speed: 9600, 19200, 38400 or 57600; Parity: no parity (2 stop bits), even or
Network parameter
odd (1 stop bit)
Analog output
0-10 V, max. 5 mA, EC fan control
Digital outputs
2 NO contacts (hot/cold), 240 V max., 500 mA load
Power supply
85 – 260 V
Absorbed power
Max 2 VA (260 V)
T° measurement range
0, + 50°C
Measurement accuracy
+/- 1°C (typical at 21°C)
Inputs
For NTC or change-over sensor
Function control
Setpoint adjustment: 0, +50°C
Screen
LCD 60 x 44 mm, 240 x 160 px, white backlighting
Functions
PI or 2/3 point control
Unit
PC, high-strength tempered glass
Protection rating
IP30 according to EN 60529 standard
Connectors
Terminals 1 to 8: 1.5 mm² max.
Ambient conditions
0, +50°C; 85% rH max. without condensation.
Weight
195 g
Assembly
Flush-mounted unit Ø60

3. CONNECTION DIAGRAM

NOTE! If 2T change-over is used, outputs 4 and 5 must be shunted
1
EC fan: Gnd
2
EC fan: 0-10 V
3
4
Cold output
5
Heat output (electric heating phase)
6
Digital input 230 V
TControl POD glass EC
7
Phase
8
Neutral (N of the electric heating)
9
NTC input 10k/floating contact
10
NTC common 10k/floating contact
11
Modbus A + (Positive)
12
Modbus B – (Negative)
TControl POD glass EC
(EC Fan, 0-10 V, 230 V)
Digital input for floating contact
Terminals 9 to 12: 1 mm² max.
230 V
3