Address-I Min. Max. Gain Name
511
0
50
0.1
512
0
50
0.1
513
0
15
0.1
514
0
50
0.1
515
0
50
0.1
516
0
1
517
0
1
518
0
10
0.1
519
0
1
520
0
1
521
-1
1
522
-1
1
523
-1
1
525
0
2
526
0
1
Modbus Input Register (R)
Heat setpoint
Cold setpoint
Setpoint offset
Internal sensor temperature
External sensor temperature
-
Heat output
-
Cold output
Ventilation status
-
Input status 1
-
Input status 2
-
In-use status
-
Dew point status
-
Window contact status
-
Control mode
-
Temperature alarm status
0-500 ≙ 0-50.0°C
Description
0-500 ≙ 0-50.0°C
Example: 21.5°C = 215
0-150 ≙ 0-15.0°C
Example: 21.5°C = 215
0-500 ≙ 0-50.0°C
Example: 3.0°C = 30
0-500 ≙ 0-50.0°C
Example: 21.5°C = 215
Example: 21.5°C = 215
0: Open
1: Closed
0: Open
1: Closed
0-100 = 0-10 V Manual
-256..-156 (=0xFF00-0xFF64): Automatic with value in
volts
0: Open
1: Closed
0: Open
1: Closed
0: Not in-use
1: In-use
-1: 0xFFFF: Input inactive
0: inactive
1: active
-1: 0xFFFF: Input inactive
0: Window closed
1: Open window
-1 = 0xFFFF: Input inactive
0: Off
1: Heat
2: Cool
0: No alarm
1: Alarm detected