SystemAir TControl POD glass EC Manuel D'installation Et De Maintenance page 27

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Address-H Min. Max. Gain Name
134
0
1
-
135
0
2
-
136
0
1
-
137
0
1
-
138
0
5
0.1
139
0
120
1
141
0
1
-
143
0
4
-
255
0
50
0.1
256
0
15
0.1
257
-1
1
-
258
-1
1
-
259
-1
1
-
260
-1
1
-
261
0
1
-
262
0
2
-
263
0
1
-
264
0
23
1
265
0
59
1
266
1
31
1
267
1
12
1
268
15
99
1
273
-
-
-
Modbus Holding Register (R/W)
Fan stage button with/without AUTO
Setpoint offset at change of in-use
mode
In-use/ECO derogation
Temperature alarm authorization
Alarm hysteresis
Alarm timer
Free/locked ventilation buttons
Pre-configuration
Basic setpoint
Setpoint offset
In-use by default
Dew point
Window contact
Change-Over
On/Off
button accessibility
Alarm activation
Hour
Minute
Day
Month
Year
Alarm clearing
TControl POD glass EC
Description
0: with AUTOMATIC (Factory setting)
1: without AUTOMATIC
0: Keep the value (Factory setting)
1: Reset the value
2: Reset the not in-use value, keep the in-use
value
0: In-use status without influence and with ECO
mode active (Factory setting)
1: Derogated in-use status in ECO mode
0: Alarm deactivated
0-50 ≙ 0-5.0°C
1: Alarm allowed (Factory setting)
0-120 ≙ 0-120 min.
Factory setting: 1 min.
Factory setting: 30 min.
0: Free buttons (Factory setting)
1: Locked buttons
0: 4P (Factory setting)
1: Changeover
0-500 ≙ 0.0 - 50.0°C
2: CO
3: HO
0-150 ≙ 0.0 - 15.0°C
Factory setting: 21.0°C
Factory setting: 0°C
0: Not in-use
1: In-use
-1: FFFF: Inactive (Factory setting)
0: dew point inactive
1: dew point active
-1: FFFF: Inactive (Factory setting)
0: window closed
1: window open
-1 = 0xFFFF: inactive (Factory setting)
0: hot mode (cold locked)
1: cold mode (hot locked)
-1 = 0xFFFF: inactive (Factory setting)
0: On (Factory setting)
1: Off
0: Free buttons (Factory setting)
1: Locked buttons
2: Locked ventilation buttons
0: alarm inactive (factory setting)
1: active alarm
0 – 23
Factory setting: 12
0 – 59
Factory setting: 0
1 – 31
Factory setting: 1
1 – 12
Factory setting: 1
15 – 99
Factory setting: 15
>0
a value >0 clears the alarm
25
EEPROM
4
4
4
4
4
4
4
4

Publicité

Table des Matières
loading

Table des Matières