SystemAir TControl POD glass EC Manuel D'installation Et De Maintenance page 25

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Address-H Min. Max. Gain Name
22
0
10
0.1
23
0
15
0.1
24
0
15
0.1
25
0
15
0.1
28
0
15
0.1
34
-
-
-
35
0
23
1
36
0
59
1
37
0
50
0.1
38
0
1
-
39
0
1
-
40
0
23
1
41
0
59
1
42
0
50
0.1
43
0
4
-
44
0
1
-
45
0
23
1
46
0
59
1
47
0
50
0.1
48
0
4
-
49
0
1
-
50
0
23
1
51
0
59
1
52
0
50
0.1
53
0
4
-
54
0
1
-
55
-
-
-
56
0
23
1
57
0
59
1
58
0
50
0.1
59
0
4
-
60
0
1
-
61
0
23
1
62
0
59
1
63
0
50
0.1
64
0
4
-
65
0
1
-
66
0
23
1
67
0
59
1
68
0
50
0.1
69
0
4
-
70
0
1
-
71
0
23
1
72
0
59
1
Modbus Holding Register (R/W)
Setpoint range
Comfort dead band
ECO mode dead band
In-use setpoint adjustment
Hysteresis
Time slot 1 Period 1: weekday
Time slot 1 Period 1: start time
Time slot 1 Period 1: start minute
Time slot 1 Period 1: Setpoint
Time slot 1: EC fan
Time slot 1 Period 1: ECO mode
Time slot 1 start time period 2
Time slot 1 start minute period 2
Time slot 1 setpoint period 2
Time slot 1 AC fan period 2
Time slot 1 ECO mode period 2
Time slot 1 start time period 3
Time slot 1 start minute period 3
Time slot 1 setpoint period 3
Time slot 1 AC fan period 3
Time slot 1 ECO mode period 3
Time slot 1 start time period 4
Time slot 1 start minute period 4
Time slot 1 setpoint period 4
Time slot 1 AC fan period 4
Time slot 1 ECO mode period 4
Time slot 2 weekdays
Time slot 2 start time period 1
Time slot 2 start minute period 1
Time slot 2 setpoint period 1
Time slot 2 AC fan period 1
Time slot 2 ECO mode period 1
Time slot 2 start time period 2
Time slot 2 start minute period 2
Time slot 2 setpoint period 2
Time slot 2 AC fan period 2
Time slot 2 ECO mode period 2
Time slot 2 start time period 3
Time slot 2 start minute period 3
Time slot 2 setpoint period 3
Time slot 2 AC fan period 3
Time slot 2 ECO mode period 3
Time slot 2 start time period 4
Time slot 2 start minute period 4
TControl POD glass EC
0-100 ≙ 0.0 - 10.0°C
Description
0-150 ≙ 0.0 - 15.0°C
Factory setting: 0.5°C
0-150 ≙ 0.0 - 15.0°C
Factory setting: 2.0°C
0-150 ≙ 0.0 - 15.0°C
Factory setting: 10.0°C
0-150 ≙ 0.0 - 15.0°C
Factory setting: 2.0°C
Factory setting: 1.0°C
Bit0: Monday
Bit1: Tuesday
Bit2: Wednesday
Bit3: Thursday
Bit4: Friday
Bit5: Saturday
Bit6: Sunday
Factory setting: 0
Example:
7 = 0x0Fhex = Monday, Tuesday, Wednesday,
Thursday
0 – 23
Factory setting: 0
0-500 ≙ 0.0 – 50.0°C
0-59 min.
Factory setting: 0
Factory setting: 21.0°C
0: Off
1: Auto (Factory setting)
0: Stop ECO mode (factory setting)
1: ECO mode activated
(#) Time slot 1 period 2
(#) Time slot 1 period 2
(#) Time slot 1 period 2
(#) Time slot 1 period 2
(#) Time slot 1 period 2
(#) Time slot 1 period 3
(#) Time slot 1 period 3
(#) Time slot 1 period 3
(#) Time slot 1 period 3
(#) Time slot 1 period 3
(#) Time slot 1 period 4
(#) Time slot 1 period 4
(#) Time slot 1 period 4
(#) Time slot 1 period 4
(#) Time slot 1 period 4
(#) Time slot 2 weekdays
(#) Time slot 2 period 1
(#) Time slot 2 period 1
(#) Time slot 2 period 1
(#) Time slot 2 period 1
(#) Time slot 2 period 1
(#) Time slot 2 period 2
(#) Time slot 2 period 2
(#) Time slot 2 period 2
(#) Time slot 2 period 2
(#) Time slot 2 period 2
(#) Time slot 2 period 3
(#) Time slot 2 period 3
(#) Time slot 2 period 3
(#) Time slot 2 period 3
(#) Time slot 2 period 3
(#) Time slot 2 period 4
(#) Time slot 2 period 4
23
EEPROM
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Publicité