Ventilation can operate in 2 modes:
permanent ventilation, ventilation operates at minimum speed even when the set temperature is
²
reached
cyclic ventilation, ventilation stops as soon as the temperature reaches the setpoint.
²
This configuration is only carried out via Modbus.
For permanent ventilation, it is enough to enter the minimum value in register 111, as shown in the table.
For cyclic ventilation, the number 32,768 must be removed from the minimum value in the table.
Example: for a minimum value of 30%, you must enter +30 - 32 768 in register 111, i.e. -32 738.
Information
As standard, the TControl POD glass EC is configured for cyclic ventilation. Configuration via the
display is only done by setting the minimum speed value. The TControl POD glass EC automatically
integrates the correction.

7.6. CONFIGURATION MENU

MENU
Time slot
Time/Date
Alarm
Fan
Configuration
Language
This menu allows you to configure a TControl POD glass EC according to 4 possibilities:
4P
: For units with 2 batteries (4 pipes).
Change-Over : For devices with a single battery but which must operate either in Cold or Heat with
automatic inversion.
CO
: For devices with only one battery and operating in Cold mode only.
HO
: For devices with only one battery and operating in Heat mode only.

7.6.1. PRE-CONFIGURATION

Setting
Input 1
Input 2 (230 V)
Ventilation selection
Post-ventilation (s)
100% ventilation hysteresis
Number of ventilation stages
4P
Change-Over
Change-Over sensor
Not used
(NTC 10k)
In-use contact NO
In-use contact NO
No
No
30
30
4
4
3
3
SELECT CONFIGURATION
4P
Change-over
CO
HO
CO
Change-Over contact
NC
In-use contact NO
No
30
4
3
HO
Change-Over contact
NO
In-use contact NO
No
30
4
3