15. MODBUS TABLES

Registers marked with a
4
not during operation!
Address-H Min. Max. Gain Name
3
0
2
-
4
-15
15
0.1
5
-15
15
0.1
6
1
2
-
7
-
-
-
8
-
-
-
10
0
2
1
11
0
5
1
12
0
5
1
13
0
5
1
14
0
5
1
15
0
5
1
18
0
12
1
19
0
10
1
20
0
50
0.1
21
0
10
0.1
are stored in the EEPROM. They may only be written during device configuration,
Modbus Holding Register (R/W)
Language
Internal sensor offset
External sensor offset
Temperature unit
Time format
Date format
Main screen display
Footer symbol 1
Footer symbol 2
Footer symbol 3
Footer symbol 4
Footer symbol 5
Universal input 1 (Low voltage)
Input 2 (230 V input)
Setpoint after voltage recovery
Setpoint range adjustment
Description
0: German
-150..150 = 15.0 - 15.0°C
1: English (Factory setting)
2: French
-150..150 = 15.0 - 15.0°C
Factory setting: 0.0°C
Factory setting: 0.0°C
1: °Celsius (Factory setting)
2: °Fahrenheit
0: 24 hour (Factory setting)
64 (=0x40): 12 hour
255 (=0xFF): Not shown on screen
0: DD.MM.YY (Factory setting)
1: YY.MM.DD
255 (=0xFF): Not shown on screen
0: Room temperature (Factory setting)
1: Setpoint
2: Setpoint offset
0: No symbol (Factory setting)
1: Heat/Cold
2: In use
3: Window contact/Dew point
4: Ventilation stage
5: Hourly programming
0: No symbol
1: Heat/Cold (Factory setting)
2: In use
3: Window contact/Dew point
4: Ventilation stage
5: Hourly programming
0: No symbol
1: Heat/Cold
2: In use
3: Window contact/Dew point
4: Ventilation stage
5: Hourly programming
0: No symbol
1: Heat/Cold
2: In use
3: Window contact/Dew point
4: Ventilation stage (Factory setting)
5: Hourly programming
0: No symbol
1: Heat/Cold
2: In use
3: Window contact/Dew point
4: Ventilation stage
5: Hourly programming
0: Not used (Factory setting)
1: NTC 10K external sensor
2: NTC 10K Change-Over sensor
3: Change-Over contact NO
4: Window contact NO
5: In-use contact NO
6: Dew point contact NO
7: Access card contact NO
8: Change-Over contact NC
9: Window contact NC
10: In-use contact NC
11: Dew point contact NC
12: Access card contact NC
0: Not used (Factory setting)
3: Change-Over contact NO
4: Window contact NO
5: In-use contact NO
6: Dew point contact NO
7: Change-Over contact NC
8: Window contact NC
9: In-use contact NC
0-500 ≙ 0.0 - 50.0°C
10: Dew point contact NC
0-100 ≙ 0.0 - 10.0°C
Factory setting: 21.0°C
Factory setting: 4.0°C
EEPROM
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4