Installation
CAUTION: Install certainly the decorative panel.
Cool air leakage causes sweating.
Good example
Fit the insulator (this part) and
be careful for cool air leakage
HEAT INSULATION
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-
resistance [over 120°C(248°F)].
2. Precautions in high humidity
circumstance:
This air conditioner has been tested
according to the "KS Standard
Conditions with Mist" and confirmed
that there is not any default. However, if
it is operated for a long time in high
humid atmosphere [dew point
temperature: more than 23°C(73.4°F)],
water drops are liable to fall. In this
case, add heat insulation material
according to the following procedure:
• Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm.
• Stick glass wool on all air conditioners that are located in ceiling atmosphere.
Drain Piping
[Standard /Artcool Mirror Type]
1. The drain hose should point downward for
optimum drainage.
2. Incorrect Installation Examples:
Do not raise
Water
Water
leakage
leakage
32 Multi Air Conditioner
Water drops fall.
Bad example
Air conditioner
unit
Ceiling
board
Decorative panel
Indoor unit
Accumulated
drain water
Tip of drain hose
Air
dipped in water
Water
Kinking
leakage
Air conditioner unit
Air
Cool air leakage
(no good)
Ceiling
board
Decorative
panel
Fastening band
(accessory)
Refrigerant piping
Thermal insulator
(accessory)
Downward slope
Flexible drain hose
Less than 50mm
(1 31/32 inch) gap
Ditch