ESP Function
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is
recommended that you should not use this function while using the remote controller.
PQRCUCS0C
Defrost
Preheat
Out door
Room Temp
Total on
Central Run
TEMP
FAN
MODE
SPEED
TEMP
Static pressure(mmAq)
Model name
Step(H/M/L)
8.5 CMM(300cfm)
AMNW09GB1A0
7.5 CMM(265cfm)
[LMDN095HV]
6.5 CMM(230cfm)
9.5 CMM(336cfm)
AMNW12GB1A0
8.5 CMM(300cfm)
[LMDN125HV]
7.5 CMM(265cfm)
15 CMM(530cfm)
AMNW18GB2A0
13.5 CMM(477cfm)
[LMDN185HV]
11.5 CMM(406cfm)
1
Press the mode button and the temperature
increasing button(L) same time for three
seconds.
2
Set the volume of each fan speed(Low, Medium, Hi)
by using the temperature control button. Press the
fan speed button to select the fan speed.
The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP
function, it will be canceled. (The picture on the left
side is the example of setting the Hi wind to ESP
10.)
4
Press the mode button and the temperature
increasing button (L) same time for three
seconds. Then the ESP setting will be activated
after the temperature display flashes three times.
EX)
Lo
200
Setting the Low wind to 210
❈ The E.S.P value is set at the proper value at the
factory. So it is highly recommended that you should
not change the E.S.P value at your discretion.
0
1
2
Setting value
75
84
94
69
77
88
62
71
83
82
90
99
75
84
94
69
77
88
90
97
105
82
90
99
75
84
93
Installation
Med
100
Setting the Medium wind to 175
3
4
104
114
99
110
95
106
109
118
104
114
99
110
114
122
109
119
103
114