Installation
[Cealing Cassette Type]
Ceiling dimension and hanging bolt location
• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
Ceiling
585~660(23 1/16~26) (Ceiling Opening)
517(20 3/8)
570(22 15/32)
Unit Size
461(18 5/32)
CAUTION :
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
NOTICE
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily
steam.
2. Avoid installng air conditioner in such places where
cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is
generated.
5. Avoid places near high frequency
generators.
26 Multi Air Conditioner
Level gauge
• Select and mark the position for fixing bolts and piping
hole.
• Decide the position for fixing bolts slightly tilted to the
drain direction after considering the direction of drain
hose.
• Drill the hole for anchor bolt on the wall.
Unit: mm(inch)
Air conditioner
Ceiling board
Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table