B
Before installing the flues, open the cabinet and fill the trap with approx. 0.5 l. of water through the flue con-
nections (see fig. 31) A and B for the model and ECONCEPT 101/101ionly A the model ECONCEPT 51/51i.
B
For outside installations make the seal 1 adhere perfectly to the top part of the cabinet, to prevent possible
infiltration of rain and atmospheric agents.
Connection with manifolds
To connect one or more modules in bank to a single flue, it is advisable to use the special manifolds (optionals) indi-
cated in the table. The choice of diameter must be made according to the total power of the bank of units, respecting
that given in the table. Use a starting kit for each bank and a suitable number of extension kits.
The starting kits have a special accessory inside them for connection also to modules ECONCEPT 51/51i. 90° bends
and manifold extensions are also available for the flue connection.
Bank heating capacity
Up to 150 kW
150 - 300 kW
300 - 500 kW
24
ECONCEPT 51/51i - 101/101i
fig. 31 - Filling the trap
Manifold diameter
Starting kit
125 mm
041008X0
160 mm
041009X0
200 mm
041010X0
cod. 3540N680 - 06/2008 (Rev. 00)
Manifold extension
Extension kit
Male-female
1000 mm
041020X0
041017X0
041011X0
041018X0
041012X0
041019X0
90° bend
for manifold
041014X0
041015X0
041016X0