Électrovanne automatique normalement fermees pour gaz à ouverture rapide

Publicité

2.0 - TECHNICAL DATA
• Ambient temperature
• Supply voltages (see table 2)
• Supply voltage tolerance
• Absorbed power
• Protection mode
• Degree of protection
• Screw class
• In compliance with
* Only single-phase, the device does not work if powered with three-phase voltage.
3.0 - COMMISSIONING THE DEVICE
3.1 - OPERATIONS PRIOR TO INSTALLATION
• It is necessary to close the gas upstream of the valve prior to installation;
• Before performing any operation, make sure that the device is not electrically powered;
• It is advisable to avoid touching the actuator with bare hands after a continuous power supply lasting longer than
20 minutes. In case of maintenance, wait for the actuator to cool down or, if necessary, use suitable protection;
NOTE: The replacement steps of the actuator must be carried out by taking care to ensure the product's IP66 protection rating.
3.2 - INSTALLATION
The installation must comply with the rules contained in standard IEC 60079-14 or with national regulations (edition
currently in force).
• Prior to carrying out any electrical wiring operations, make sure that the mains voltage matches the supply voltage indicated
on the product label.
Cut out power prior to proceeding with the wiring. Power to the actuator must not be restored until all the wiring
operations have not been completed; the actuator must not be opened while it is energised.
Do not open in the presence of an explosive atmosphere.
Remove the safety screw (4) using a suitable Allen wrench, then unscrew and remove the closing cap (6).
Unscrew the central screw (5) of the connector (8), remove it and subsequentlyconnect terminals 1 and 2 to the power
supply and the earthing cable to the terminal
To wire the connector, use a cable type H05SS-K 3X0.75 mm², external Ø from 6.2 to 8.1 mm, with suitable length
and protection. Use the special cable terminals (see fig. 7). Minimum cross-section of the earthing conductor equal to line
conductors. Once the wiring is done, position and secure it as originally positioned.
Also carry out the earthing connection on screw (3) using a special eyelet (not supplied). Insert, in the following
sequence, eyelet, toothed washer, then tighten with the screw (3). The equipotential bonding must be managed using a
cable with a section not less than 4mm
CPS19... - CPS25...
: -40 ÷ +55 °C / -40 ÷ +60 °C (see product label)
: 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: see table 2
: capsule Ø int. 19mm:
capsule Ø int. 25mm:
capsule Ø int. 25mm:
: IP66 According to EN / IEC 60529 standard
(only if installed on a solenoid valve fitted with suitable gaskets)
: 8,8 for models CPS19...
10,9 for models CPS25...
(The head of screws, for models CPS25-E and CPS25S-E, is in accordance
with ISO 10642. They must be replaced only with identical ones).
: Directive ATEX 2014/34/EU
EN IEC 60079-0:2018 / IEC 60079-0:2017
EN 60079-1:2014 / IEC 60079-1:2014
. IMPORTANT: with a 24 VDC power supply, comply with the polarity.
.
2
8
II 2G Ex db IIC T5 Gb
II 2G Ex db IIC T5 Gb
II 2G Ex db IIC T4 Gb
Madas Technical Manual - 1|1.6c - REV. 0 of 3
(-40 ÷ +60 °C)
(-40 ÷ +55 °C)
(-40 ÷ +60 °C)
Feb 2022
rd