Example:
V
= 1.5 FT (0.5m)
1
V
= 5 FT (1.5m)
2
V
= V
+ V
= 1.5FT (0.5m)+ 5FT (1.5m) = 6.5 FT (2m)
T
1
2
H
= 1 FT (0.3m)
1
H
= 1 FT (0.3m)
2
H
= 10.75 FT (3.3m)
3
H
= H
+ H
+ H
= 1FT (0.3m) + 1FT (0.3m) + 10.75FT (3.3m) = 12.75FT (3.9m)
R
1
2
3
H
= .03 (three 90° elbows + one 45° elbow - 90°)
O
= .03 (270° + 45° - 90°) = 6.75 FT (2.1m)
H
= H
+ H
= 12.75FT (3.9m) + 6.75FT (2.1m) = 19.5 FT (5.9m)
T
R
O
H
+ V
= 19.5FT (5.9m) + 6.5FT (2m) = 26 FT (7.9m)
T
T
Formula 1:
H
< 3 V
T
T
3 V
= 3FT (0.9m) x 6.5FT (2m) = 19.5FT (5.9m)
T
19.5FT (5.9m) = 19.5FT (5.9m)
Formula 2:
H
+ V
< 40 FT (12.2m)
T
T
26 FT (7.9m) < 40 FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
2.10
rear exit
WARNING
!
•
Failure to create a seal to the firebox with the exhaust collar assembly will cause the appliance to function
improperly and can cause injury or property damage.
Remove the safety barrier and glass front, refer to "safety
A.
barrier & door removal/installation" section.
Remove the contents from the firebox and set aside, you will
B.
need the exhaust flue collar from the top of the log carton.
To ease assembly, remove the four hex head screws
C.
securing the deflector from inside the top front of the firebox,
refer to Figure 1. Set deflector aside.
Place the gasket (provided) over the 4" (102mm) flue collar
D.
assembly and bend along perforation.
From inside the firebox, insert the 4" (102mm) flue collar through the back
E.
of the firebox. Install the rear exit shield onto the 4" (102mm) flue collar, see
"rear exit shield" section for installation instructions.
Secure the flue collar assembly, gasket and rear exit shield using the four hex
F.
head 3/8" thread cutting screws, refer to Figure 2.
note:
Do not overtighten. The gasket needs only to be
snug against the firebox.
Reattach the deflector using the four screws and
G.
install the log set, glass door and safety barrier.
Remove the four screws securing the gasket and
H.
the outer coverplate. Install the 7" collar assembly,
complete with gasket, onto the rear panel around
the 4" collar (Fig. 3).
Secure the gasket (provided in manual baggie) and
I.
the outer cover plate over the top opening of the
appliance.
venting requirements
90°
H
2
45°
V
1
H
1
90°
Fig. 1
DEFLECTOR
DÉFLECTEUR
V
2
90°
H
3
18.2_3B
Fig. 2
Fig. 3
GASKET
INTAKE COLLAR
ASSEMBLY
W415-2944 / B / 05.22.24
EN