The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
venting requirements
be combined.
EN
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs must have a 1" rise per foot on a 20" (50.8cm) rear vent application. However, for optimum performance, it is
Horizontal runs may have a 0" rise per foot or 0mm rise per meter however for optimum performance it is recommended
recommended that all other horizontal runs have a minimum 1/4" rise per foot or 21mm rise per meter using flexible venting.
that all horizontal runs have a minimum 1/4" rise per foot or 21mm rise per meter using fl exible venting. For safe and proper
For safe and proper operation of the appliance, follow the venting instructions exactly.
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" (31.8mm) air gap
all around between the inner liner and outer liner is required for safe operation.
This appliance is certified for use with a power vent kit. Contact your local authorized dealer for more information.
If approved for use with a power vent kit, state: "This appliance is certifi ed for use with a
power vent kit. Contact your local authorized dealer for more information."
If not, cover with a white box.
** When a vertical rise is used as part of the venting configuration, a 0" (0mm) rise per foot is acceptable.
14
W415-2944 / B / 05.22.24
GX36-1 REQUIRED RISE ON HORIZONTAL
VENTING
DRAFT
Rear Vent
Rigid Venting
Flexible Venting
Rigid Venting
Top Vent
Flexible Venting
Rigid Venting
Rear Vent
Corner
Flexible Venting
1" (25mm) / FT**
1" (25mm) / FT**
0" / FT
0" / FT
6" (152mm)
6" (152mm)