Spare Parts; Electrical Diagram; Disposal; Ce Declaration - PLYMOVENT ControlPro Manuel D'installation

Masquer les pouces Voir aussi pour ControlPro:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Symptom
problem
White LED
No indication
remains off
Filter and/or
No pressure
fan pressure
indication
value = 0
when system
is on
Filter and/or
Wrong
fan pressure
pressure
value ≠ 0
indication
when system
is off
Fillter
Wrong
pressure
pressure
value is
indication
negative or
illogical
Malfunction of
Fan pressure
frequency
value is
inverter
negative
USB stick is
Firmware
not
update not
recognized
possible
Filter system
Filter cleaning
No optimum
sequence is
cleaning
incorrect or
performance
illogical
9

SpaRE paRtS

The following spare parts are available for the product.
9.1
controlpro/panel
Refer to exploded view Fig. VI on page 83.
article no.
Description
0000103139
Switch mode power supply 24V DC 2.5A
0000103141
Rotary switch 0-1
0000113558
Indicator light yellow 24V
0000113559
PCB main board ControlPro
0040900180
Main switch 25A
0324000300
Indicator light white 24V
0324000310
Indicator light green 24V
0324000320
Indicator light red 24V
0328050300
Push button green
0328050320
Push button black
0360000060
Buzzer
9.2
controlpro/hMi
Refer to exploded view Fig. VII on page 83.
article no.
Description
0000112777
ControlPro/HMI (complete)
0000113560
Dust cap for ControlPro/HMI
0000112606/200917/0 ControlPro
possible
Solution
cause
LED is defective
Replace the LED
Loose
Connect the
pneumatic
hose(s)
hose(s)
Wrong pressure
Do a zero point
setting
calibration of the
internal sensors
(refer to screen
1.2)
One pneumatic
Connect the hose
hose is loose
Inverted
Correct the
connection of
connection (refer to
the pneumatic
par. 4.5.1)
hoses (+ vs. –)
Wrong type of
Set the correct type
external
of pressure sensor
pressure sensor
(refer to screen
configured
1.2)
(PT-1000 vs.
PT-2500)
Wrong
Correct the
connection of
connection (refer to
the pneumatic
par. 4.5.2)
hose (+ vs. –)
USB-stick does
Use a USB 2.0 or
not comply with
USB 3.0 stick
USB 2.0
standard (too
slow)
Addressing
Correct the setting
sequence is not
of the DIP
correct
switches; refer to
Fig. 4.18
9.3
control/SlaveBoard
Refer to exploded view Fig. VIII on page 83.
article no.
Description
0000113561
PCB slave board
10

ELEctRicaL DiagRaM

Refer to the separately supplied electrical diagram.
11

DiSpoSaL

After life of the product, dispose it of in accordance with
federal, state or local regulations.

cE DEcLaRatioN

CE Declaration of Conformity for machinery
We, Plymovent Manufacturing B.V., Koraalstraat 9, 1812 RK
Alkmaar, the Netherlands, herewith declare, on our own
responsibility, that the product:
- ControlPro
which this declaration refers to, is in accordance with the
conditions of the following:
Directives:
- EMC 2014/30 EU | EMC Directive
- LVD 2014/35 EU | Low Voltage Directive
Harmonised Standards:
- EN-IEC 60204-1:2006 | Safety of machinery - Electrical
equipment of machines - Part 1: General requirements
- EN-IEC 61439-1:2011 | Low-voltage switchgear and
controlgear assemblies - Part 1: General rules
- EN-IEC 61131-2:2007 | Programmable controllers - Part 2:
Equipment requirements and tests
- EN-IEC 61000-6-2:2005 | Electromagnetic compatibility
(EMC) - Part 6-2: Generic standards - Immunity for industrial
environments
- EN-IEC 61000-6-4:2007 | Electromagnetic compatibility
(EMC) - Part 6-4: Generic standards - Emission standard for
industrial environments
Alkmaar, Netherlands, 1 October 2017
Jeroen Crezee
Manager R&D
An installation is defined as a combination of several finished products
or components that are assembled by an installer at a given place. The
various parts of the installation are intended to operate together in a
particular environment and to perform a specific task. The entire
installation must comply with the relevant directives and standards. The
assembly instructions given by the manufacturer, as well as the whole
method of installation, must be in accordance with good engineering
practices within the context of installations, as well as installation rules.
Considering the above, the installer will be responsible for completing
the installation and issuing the final CE Declaration of Conformity.
EN - 17

Publicité

Table des Matières
loading

Table des Matières