11. Testing the automatic gate system.
It is necessary to test all the accessories connected to the control unit, especially the safety devices such as the sensitive edges and photocells.
Remember that the photocells reverse the movement of the gate only during closing and the sensitive edges and/or internal photocells, if engaged
during opening, reverse the movement of the gate for 1.5 seconds, while if engaged when closing they fully re-open the gate.
12. Trimmer for adjustments.
Trimmer
Function
TR1 - DELAY
Pause time
TR2 - TORQ
Motor torque
TR3 - SL
Deceleration speed
13. Dip switch functions.
Num-
Sta-
Function
ber
tus
OFF
Automatic closing disabled
DIP 1
ON
Automatic closing enabled
OFF
Operating logic: Opens-Stops-Closes-Stops
DIP 2
ON
Operating logic: Opens-Closes
OFF
Courtesy function on photocell disabled
DIP 3
ON
Courtesy function on photocell enabled
OFF
Collective operating logic disabled
DIP 4
ON
Collective operating logic enabled
OFF
Pre-flashing disabled
DIP 5
ON
Pre-flashing enabled
OFF
Flashing controlled by the control unit.
DIP 6
ON
Flashing built into the flashing lamp.
OFF
Hammering disabled
DIP 7
ON
Hammering enabled
OFF
Force adjustment enabled.
DIP 8
ON
Force adjustment disabled.
OFF
"Soft" start disabled
DIP 9
ON
"Soft" start enabled
OFF
Output +P.OUT for 2
DIP 10
ON
Output +P.OUT for safety device test.
OFF
Input P.IN normally open
DIP 11
ON
Input P.IN normally closed
OFF
Sensitive edge
DIP 12
ON
Sensitive edge with resistive load 8.2 Kohm
Description
With Dip switch 1 ON, it adjusts the amount of time during
which the gate remains stationary before automatic closing.
With Dip switch 8 OFF, it adjusts the motor torque.
It adjusts the deceleration speed.
If turned completely clockwise, deceleration is excluded
radio channel.
nd
with electro-mechanical switch
Description
-
The open gate is
closed automatically after the pause time.
It modifies the operating sequence of inputs SEQ (sequential) and PED
(pedestrian) also via remote control.
-
Reduction to 5sec of the residual pause time after passing over photocells.
-
When opening the gate ignores any controls and reloads the pause time
when on pause.
-
3 seconds before the start of each movement, the flashing lamp begins to
flash.
It configures the output for flashing lamps without independent flashing.
It configures the output for flashing lamps with independent flashing.
-
It generates instant hammering to hook (at the end of closing) or release
(at the beginning of opening) the electrical lock.
Possibility of adjusting the force of the motors using trimmer TR2 TORQ.
Motor force at maximum. Trimmer TR2 TORQ disabled.
-
It slows down the start of each movement.
It enables use of the 2
remote control channel.
nd
It checks the operation of the safety devices if connected to +P.OUT.
For use on a possible open-only push button
For use on a possible sensitive edge
It configures the type of sensitive edge. In only operates with DIP 11 ON
EN
Range
From 1 to 130 seconds, maximum,
clockwise
From 20 to 100%, maximum,
clockwise
From 0 to 100%, maximum, clock-
wise
35